KL4414, KL4424 - Product Overview
KL4414, KL4418, KL4424, KL4428
9
Version: 3.0.0
2.2
Technical data
Technical data
KL4414
KL4424
Number of outputs
4
Output current
0 mA ... 20 mA
4 mA ... 20 mA
Load
< 350 Ω (short-circuit-proof)
Supply for the outputs
24 V
DC
(or 15 V
DC
with KL9515 power supply terminal) via the power
contacts
Resolution
12 bits
Accuracy
0.1%
Conversion time
approx. 4 ms
Electrical isolation
500 V (K-bus/signal voltage)
Power supply for the electronics
via the K-bus and through the power contacts
Current consumption from K-bus
typically 20 mA (5 V)
Current consumption from power
contacts
typically 40 mA (24 V)
Bit width in process image
Output: 4 x 16 bits user data, 4 x 8 bits control/status (optional)
Weight
approx. 80 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN 60715
Permissible ambient temperature
range during operation
0 °C ... + 55 °C
Permissible ambient temperature
range during storage
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6/EN 60068-2-27, see also
instructions for enhanced mechanical load capacity [
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE, UL,
, GL