KS2000 Configuration Software
KL3356
31
Version: 2.3.0
Manufacturer scaling active (
)
You can activate manufacturer scaling here (default: disabled).
Scale factor active (
)
You can deactivate the scale factor here (default: enabled).
You can deactivate the watchdog timer here (default: enabled).
You can deactivate cyclic calibration here (default: enabled).
Cyclic reference measurement enabled (
You can deactivate cyclic reference measurement here (default: enabled).
)
You can deactivate cyclic testing here (default: enabled).
Symmetric reference potential (
You can deactivate the symmetric reference potential here (default: enabled).
Stabilization of calibration active (
You can deactivate the stabilization of the calibration here (default: enabled). The stabilization of the
calibration can be parameterized via the parameters "number of stable measured values" and "tolerance for
measurement stability".
Resolution of nominal parameter 0.01 mV/V (
)
Here you can enable a resolution of nominal parameter of 0.01 mV/V, instead of the resolution of nominal
parameter of 1 mV/V (default: disabled).
After calibration wait for stable value (
Here you can specify that, after calibration or measurement of the reference voltage, the KL3365 should wait
until the weight value output is stable before outputting the measured value (default: disabled).
Register data
You can specify the nominal weight of the connected load cell here in kg (default: 5 kg).
You can specify the nominal characteristic value of the connected load cell here (default: 2 mV / V).
You can specify the scale factor here (default: 1000).
Measure interval for the reference signal (
)
You can specify the measuring interval for the reference signal here in steps of 100 ms (default: 360 s).