Access from the user program
KL3356
49
Version: 2.3.0
Recommended values
Value in R37
F
stop
Cycle time
0x35C0
50 Hz
140 ms
0x2660
70 Hz
100 ms
0x1330
140 Hz
50 ms
0x7FF1
40 ms
0x3FF1
20 ms
0x1001
<4 ms
Value in R37
F
limit
Cycle time
0x7FF2
39.6 Hz
40 ms
0x3FF2
77.36 Hz
20 ms
0x1002
158 Hz
<4 ms
R38: scaling factor
This register contains the scale factor.
Examples:
0x0001 (01
dec
) means factor 1
0x000A (10
dec
) means factor 10
The scale factor can be enabled through bit
R39: Measuring interval for reference signal
This register contains the measuring interval for the cyclic reference measurement. The unit is 100 ms. The
cyclic reference measurement can be enabled through bit
R40: Calibration interval
This register contains the calibration interval for the terminal's automatic calibration. The unit is 100 ms. The
automatic calibration can be enabled through bit
in the feature register.
R41: Test interval
This register contains the test interval for the terminal's cyclic testing. This interval is always a multiple
(default: 3
dec
) of the calibration interval (R40). The test interval when the terminal leaves the factory is
therefore 10 x 180 s = 1800 s. The cyclic testing can be enabled through bit
register.
R42: nominal test value
This register contains the terminal's nominal test value.
During the production of the terminal, the actual test value is transferred from register 5 to the nominal test
value register R42. This value provides information about a voltage resulting from an internal reference
voltage source and a voltage divider.
During a calibration, the system checks whether the value is within the tolerance given by registers R42 and
R43. This can be used to determine whether there is an internal defect (e.g. faulty analog switch).
This value may change slightly over time (due to ageing of the electrical components). If necessary, the
actual test value of register R5 should therefore be transferred to register R42 from time to time. This can be
done safely, because in case of an error the value will approach 0 or 65535.
R43: test tolerance
This register contains the test tolerance of the terminal (+/-).