background image

Appendix 

 

20 

KL304x and KL305x 

 
 

Support and Service 

 

 

BECKHOFF

 and their partners around the world offer comprehensive service 

and support, making available fast and competent assistance with all 
questions related to 

BECKHOFF

 products and system solutions. 

 

 

BECKHOFF Support 

Support offers you comprehensive technical assistance, helping you not 
only with the application of individual BECKHOFF products, but also with 
other, wide-ranging services: 

 

world-wide support 

 

design, programming and commissioning of complex automation 
systems 

 

and extensive training program for BECKHOFF system 
components 

 
Hotline:  

+49(0)5246/963-157

 

Fax: 

 

+49(0)5246/963-199

 

e-mail:   

[email protected]

 

 

 

 

 

BECKHOFF Service 

The BECKHOFF Service Centre supports you in all matters of after-sales 
service: 

 

on-site service 

 

repair service 

 

spare parts service 

 

hotline service 

 
Hotline:  

+49(0)5246/963-460

 

Fax: 

 

+49(0)5246/963-479

 

e-mail:   

[email protected]

 

 
 
 

 

BECKHOFF company headquarters 

Beckhoff Automation GmbH 
Eiserstr. 5 
D-33415 Verl 
Germany 
 
Phone:   

+49(0)5246/963-0

 

Fax: 

 

+49(0)5246/963-198

 

e-mail:   

[email protected]

 

 
 
The addresses of 

BECKHOFF

's branch offices and representatives round the 

world can be found on the internet pages: 

 

http://www.beckhoff.com

 

 

You will also find further documentation for 

BECKHOFF

 components there. 

 

Summary of Contents for KL3041

Page 1: ...1 KL3042 and KL3044 Single Two and Four Channel Analog Input Terminals Measuring range 0 to 20 mA and KL3051 KL3052 and KL3054 Single Two and Four Channel Analog Input Terminals Measuring range 4 to 2...

Page 2: ...KL3041 and KL3051 2 KL3042 and KL3052 3 KL3044 and KL3054 3 4 Functional description 4 5 Terminal configuration 6 6 Register Description 7 General Description of Registers 7 Terminal specific register...

Page 3: ...e of the statements of this manual represents a guarantee Garantie in the meaning of 443 BGB of the German Civil Code or a statement about the contractually expected fitness for a particular purpose i...

Page 4: ...s signal voltage Current consumption from K Bus typically 65 mA Bits width in process image Input 1 x 16 bits of data 1 x 8 bit control status optional Input 2 x 16 bits of data 2 x 8 bit control stat...

Page 5: ...Connection KL304x and KL305x 3 KL3042 and KL3052 KL3044 and KL3054...

Page 6: ...hown in two s complement form integer 1 corresponds to 0xFFFF Other display types can be selected via the feature register e g sign amount representation Siemens output format Measured value Output KL...

Page 7: ...h Manufacturer scaling R19 R20 B_w A_w User scaling R33 R34 a Neither user nor manufacturer scaling are active Y_a B_a X_adc A_a 1 0 Y_aus Y_a b Manufacturer scaling active factory setting Y_1 B_h A_h...

Page 8: ...erminal2 Channel2 8 User data allocation depending on mapping K Bus Beckhoff Lightbus bus coupler BK2000 To the bus terminal L H C S 0 D0 0 D0 1 D1 0 D1 1 C S 1 C S C S Data L Data H Data H Data L C S...

Page 9: ...r manual under Master configuration i Note The Appendix contains an overview of possible mapping configurations depending on the parameters that can be set Parameterization with KS2000 The parameteriz...

Page 10: ...iagnostic register can contain additional diagnostic information Parity errors for instance that occur in serial interface terminals during data transmission are indicated here R7 Command register Hig...

Page 11: ...r The manufacturer parameters are stored in a serial EEPROM in the terminal and are retained in the event of voltage drop out These registers can only be altered after a code word has been set in R31...

Page 12: ...gister contains the offset of the manufacturer s equation of the straight line 1 3 The straight line equation is activated via register R32 R20 Manufacturer scaling gain A_h 16 bits signed integer 2 1...

Page 13: ...1 active 0 The process data are compared with limit value 1 R35 and appropriate status bits are set Bit 10 1 Limit value 2 active 0 The process data are compared with limit value 1 R36 and appropriate...

Page 14: ...wing filter constants can be selected in R37 not possible for KL3044 and KL3054 In the standard setting the corresponding conversion time is 2 5 ms R37 Explanation 0x0000 2nd order FIR filter default...

Page 15: ...tion function is activated Bit 4 1bin Gain compensation Bit 3 1bin Offset compensation Bit 2 0bin Slower cycle 1000 ms 1bin Fast cycle 50 ms Bit 1 1bin up Bit 0 1bin down Status byte for process data...

Page 16: ...ister that is to be addressed is entered into bits 0 to 5 of the control byte Control byte in register mode MSB REG 1 W R A5 A4 A3 A2 A1 A0 REG 0bin Process data exchange REG 1bin Access to register s...

Page 17: ...yte 3 Byte 2 Byte 1 Byte 0 Name DataIN 1 DataIN 0 Not used Status byte Value 0x0B 0xE2 0x00 0x88 Example 2 Writing of register 31 in the BK2000 with an intelligent terminal and the end terminal If the...

Page 18: ...ignment any 2 Default mapping for CANopen CANCAL DeviceNet ControlNet Modbus RS232 and RS485 Coupler 3 Conditions Word offset High byte Low byte Complete evaluation no 0 Ch1 D0 Ch1 D1 Motorola format...

Page 19: ...Word offset High byte Low byte Complete evaluation yes 0 res Ch1 CB SB Motorola format no 1 Ch1 D1 Ch1 D0 Word alignment yes 2 res Ch2 CB SB Default mapping for Lightbus and Ethernet Coupler and Bus T...

Page 20: ...1 Ch2 D0 3 Ch3 D0 Ch3 CB SB 4 Ch4 CB SB Ch3 D1 5 Ch4 D1 Ch4 D0 Conditions Word offset High byte Low byte Complete evaluation yes 0 Ch1 D1 Ch1 CB SB Motorola format yes 1 Ch2 CB SB Ch1 D0 Word alignmen...

Page 21: ...egister variable R W RAM R16 Hardware version number 0x R W SEEROM R17 Hardware compensation offset specific R W SEEROM R18 Hardware compensation gain specific R W SEEROM R19 Manufacturer scaling Offs...

Page 22: ...nsive training program for BECKHOFF system components Hotline 49 0 5246 963 157 Fax 49 0 5246 963 199 e mail support beckhoff com BECKHOFF Service The BECKHOFF Service Centre supports you in all matte...

Reviews: