Access from the user program
KL2791
33
Version: 2.0.0
Key
Bit
Name
Description
SB.7
RegAccess
0
bin
Acknowledgment for process data mode
SB.6
Error
1
bin
A load-side short circuit was detected
SB.5
Temperature warning
1
bin
Overtemperature detected (> 80°C): The process data
are limited to 20% (the limitation is automatically reset
when the temperatures falls below 60°C)
SB.4
Overload
1
bin
Overload detected (e.g. when switching higher loads
on)
SB.3 to SB.1
Operation mode
0
dec
Full-wave control
1
dec
Mixed control
SB.0
Synchronous
0
bin
Terminal is not synchronized with the mains or a short
circuit was detected on the load side
1
bin
Terminal has synchronized itself with the mains*
Register communication
Control byte (for register communication)
The control byte (CB) is located in the
, and is transmitted from the controller to the
terminal.
Bit
CB.7
CB.6
CB.5
CB.4
CB.3
CB.2
CB.1
CB.0
Name
RegAccess R/W
Reg. no.
Key
Bit
Name
Description
CB.7
RegAccess
1
bin
Register communication switched on
CB.6
R/W
0
bin
Read access
1
bin
Write access
CB.5 to CB.0
Reg. no.
Register number:
Enter the number of the
- want to read with input data word
- want to write with output data word
.
Status byte (for register communication)
The status byte (SB) is located in the
, and is transmitted from terminal to the controller.
Bit
SB.7
SB.6
SB.5
SB.4
SB.3
SB.2
SB.1
SB.0
Name
RegAccess R/W
Reg. no.
Key
Bit
Name
Description
SB.7
RegAccess
1
bin
Acknowledgment for register access
SB.6
R
0
bin
Read access
SB.5 to SB.0
Reg. no.
Number of the register that was read or written.