Access from the user program
KL2791
32
Version: 2.0.0
6
Access from the user program
6.1
Process image
The KL2791 is represented in the complex process image with 3 bytes of input data and 3 bytes of output
data. These are organized as follows:
Byte offset (without
word alignment)
Byte offset (with word align-
ment*)
Format Input data
Output data
0
0
Byte
1
2
Word
DataIN
DataOUT
The KL2791 is represented in the compact process image without input data and with 2 bytes of output
data. These are organized as follows:
Byte offset (without
word alignment)
Byte offset (with word align-
ment*)
Format Input data
Output data
0
0
Word
-
DataOUT
*) Word alignment: The Bus Coupler places values on even byte addresses
Key
SB: Status byte
CB: Control byte
DataIN: input word
DataOUT: output word
In process data mode, the output word DataOUT controls the output power of the speed controller terminal.
Valid values are 0
dec
to 32767
dec
.
6.2
Control and status bytes
Process data mode
Control byte (for process data mode)
The control byte (CB) is located in the
, and is transmitted from the controller to the
terminal.
Bit
CB.7
CB.6
CB.5
CB.4
CB.3
CB.2
CB.1
CB.0
Name
RegAccess -
-
-
-
-
-
-
Key
Bit
Name
Description
CB.7
RegAccess
0
bin
Register communication off (process data mode)
CB.6 to CB.0
-
0
bin
reserved
Status byte (for process data mode)
The status byte (SB) is located in the
, and is transmitted from terminal to the controller.
Bit
SB.7
SB.6
SB.5
SB.4
SB.3
SB.2
SB.1
SB.0
Name
RegAccess Error
Temperatur
e warning
Overload
Operation mode
Synchrono
us