Product overview
KL2602, KL2622, KL2634
14
Version: 2.4.0
KL2602-0010 and KL2622-0010
Technical data
KL2602-0010
KL2622-0010
Number of outputs
2 x make contacts for power
contact
2 x make contacts
Contact material
Ag-Alloy (Au plating applied to stationary contact)
Rated load voltage
230 V
AC
/ 30 V
DC
Load type
ohmic, inductive, capacitive
Switching current max.
typ. 5 A
AC/DC
each channel
Switching current inductive
typ. 2 A
AC/DC
each channel
Minimal permissible load
typ. 0.1 mA at 0.1 V
DC
Electrical isolation
500 V (K-bus/field potential)
K-Bus current consumption
80 mA
85 mA
Bit width in the process image
2 outputs
Reaction time at a rated load
max. 20 ms (= 10 ms zero crossing voltage delay at
50 Hz + 10 ms delay time of the relay)
Operating cycles mech. (min.)
2 x 10
7
(at 18 x 10
3
switching cycles per hour)
Operating cycles electr. (min.)
100,000 (3 A at 250 V
AC
, 3 A at 30 V
DC
and ohmic load)
80,000 (5 A at 250 V
AC
, 5 A at 30 V
DC
and ohmic load)
100,000 (2 A at 250 V
AC
, 2 A at 30 V
DC
and inductive load)
Configuration
no address or configuration settings
Special features
Soft switching at the zero voltage crossing
Contact resistance (max.)
typ. 100 mΩ
Insulation resistance (min.)
typ. 1000 MΩ at 500 V
DC
Weight
approx. 50 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Permissible ambient temperature range
during operation
0…+55 °C
Permissible ambient temperature range
during storage
-25…+85 °C
Permissible relative humidity
95 %, no condensation
on 35 mm mounting rail according to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Installation position
Variable
Protect. class
IP20
Approvals
CE, cULus
Summary of Contents for KL2602 Series
Page 2: ......