Product overview
KL1xxx
17
Version: 1.0.0
2-channel digital input terminal 24 V
DC
, type 3
The KL1402 and KL1412 supplement the proven KL1404, KL1414, KL1408 und KL1418 digital input
terminals with their type-3 specification. The current/voltage characteristics have been optimized for 2-wire
sensors. The input current in low state is increased to a minimum value of 1.5 mA and therefore supports the
majority of commercially available 2-wire sensors. A typical value for the energy-saving high current is
2.2 mA. The input complies with the EN 61131-2 type 3 standard and is compatible with type 1.
2.4.1
KL1402, KL1412 – Technical data
Technical data
KL1402, KS1402
KL1412, KS1412
Connection technology
4-wire
Number of inputs
2
Nominal voltage
24 V
DC
(-15 %/+20 %)
Signal voltage ‘0’
-3 V to +5 V (EN 61131-2, type 1/3)
Signal voltage ‘1’
11 V to 30 V (EN 61131-2, type 3)
Signal current “0”
0 to 1.5 mA
Signal current "1"
2.0 to 2.5 mA
Input filter
typically 3.0 ms
typically 0.2 ms
Current consumption from K-bus
typically 3 mA
Current consumption power
contacts
typ. 1 mA + load
Electrical isolation
500 V (K-bus / field voltage)
Bit width in process image
2 inputs
Configuration
no address or configuration settings required
Weight approx.
50 g
Permissible ambient temperature
during operation
0°C ... +55°C
Permissible ambient temperature
during storage
-25°C ... +85°C
Permissible relative humidity
95%, no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity [
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Pluggable wiring
for all KSxxxx terminals
Approvals
CE, cULus,
, GL