TwinCAT configuration
FC1028
17
Version: 1.0
1. Click on the left side in the tree view on an EtherCAT master that you want to configure for cable
redundancy.
2. Click on the
EtherCAT
tab, then
Advanced Settings
.
3. Click on
Redundancy
in the tree structure on the left.
4. Click on the
Adapter Reference
option and then select a second EtherCAT master from the drop-down
menu.
ð
You have successfully configured cable redundancy. The EtherCAT slaves configured for cable
redundancy are displayed in the
Online
tab.
Summary of Contents for FC1028
Page 1: ...Manual EN FC1028 PCIe EtherCAT Master Card 5 9 2022 Version 1 0...
Page 2: ......
Page 4: ...Table of contents FC1028 4 Version 1 0...
Page 31: ......