Operation
EP1918
32
Version: 1.1.0
Under the
Connection
tab you can make further settings, e.g. the mapping of the info data or the behavior in
case of a module error.
Fig. 21: Connection tab of the EP1918
Name
Description
Conn. no.
Connection number (issued by the system)
Conn. Id
Connection ID:
Pre-allocated by system, can be changed by the user. The connection ID must be
unique within the TwinCAT project.
Mode
• FSoE master (the logic is the master for this alias device)
• FSoE slave (the logic is a slave for this alias device)
Watchdog
Setting the watchdog time in ms for this connection. This setting directly affects
the fault response time.
Module Fault is ComError If the checkbox is checked, module error also triggers a ComError, which
switches the TwinSAFE group where the connection was created to the error
state.
Com ERR Ack
For each connection, an additional error acknowledge can be configured. In this
case, the connection must also be acknowledged, in addition to the Err Ack for
the respective group.
Map state
The connection state is placed in the cyclic process data.
Map diag
The connection diagnostics is placed in the cyclic process data.
Map inputs
The safe input information of the connection is placed in the cyclic process data.
Map outputs
The safe output information of the connection is placed in the cyclic process data.