Operation
EP1918
18
Version: 1.1.0
4.2.2.2
EtherCAT connection
The EtherCAT Box (EPxxxx) has two M8 connectors marked
green
for the incoming and outgoing EtherCAT
connection.
Fig. 8: EtherCAT connection 30 mm housing M8
Connection
There are various different standards for the assignment and colors of connectors and cables for EtherCAT.
EtherCAT
Connector
Cable
Standard
Signal
Description
M8
ZB9010, ZB9020,
ZK1090-6292
ZB903x,
ZK1090-31xx
TIA-568B
Tx +
Transmit Data+ Pin 1
yellow
1
orange/white
2
white/orange
Tx -
Transmit Data-
Pin 4
orange
1
orange
2
orange
Rx +
Receive Data+
Pin 2
white
1
blue/white
2
white/green
Rx -
Receive Data-
Pin 3
blue
1
blue
2
green
Shield
Shield
Housing
Shield
Shield
Shield
1)
Core colors according to EN 61918
2)
Core colors
4.2.2.3
EtherCAT cables
For connecting EtherCAT devices only Ethernet cables that meet the requirements of at least
category 5
(CAT5) according to EN 50173 or ISO/IEC 11801
should be used.
Wiring recommendations
Detailed recommendations for EtherCAT wiring can be found in the documentation "Design recom-
mendations for EtherCAT/Ethernet infrastructure", which is available for download from
EtherCAT uses four cable wires for signal transmission. Due to automatic cable detection (auto-crossing)
symmetric (1:1) or cross-over cables can be used between EtherCAT devices from BECKHOFF.