Operation
EL6900
29
Version: 2.2.0
Manufacturer
Type
Comment
Beckhoff
AX5801
TwinSAFE Drive option card: safe restart lock
Beckhoff
AX2000 AS option
safe restart lock
Siemens
SIRIUS series S00
3RT1016-1BB42
Contactor
Telemecanique
LP1K09
Contactor
The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.
Note
Recommended protective circuits
We recommend R/C or diode-based protective circuits for these devices.
Varistor-based protective circuits should not be used.
4.3
Operation in potentially explosive atmospheres (ATEX)
4.3.1
Special conditions
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus
components in potentially explosive areas (directive 94/9/EU)!
The certified components are to be installed in a suitable housing that guarantees a protec-
tion class of at least IP54 in accordance with EN 60529! The environmental conditions dur-
ing use are thereby to be taken into account!
If the temperatures during rated operation are higher than 70 °C at the feed-in points of ca-
bles, lines or pipes, or higher than 80°C at the wire branching points, then cables must be
selected whose temperature data correspond to the actual measured temperature values!
Observe the permissible ambient temperature range of 0 to 55 °C when using Beckhoff
fieldbus components in potentially explosive atmospheres!
Measures must be taken to protect against the rated operating voltage being exceeded by
more than 40% due to short-term interference voltages!
The individual terminals may only be unplugged or removed from the Bus Terminal system
if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!
The connections of the certified components may only be connected or disconnected if the
supply voltage has been switched off or if a non-explosive atmosphere is ensured!
The fuses of the EL92xx power feed terminals may only be exchanged if the supply voltage
has been switched off or if a non-explosive atmosphere is ensured!
Address selectors and ID switches may only be adjusted if the supply voltage has been
switched off or if a non-explosive atmosphere is ensured!
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0: 2006
• EN 60079-15: 2005
Summary of Contents for EL6900
Page 1: ...Operating Instructions for EL6900 TwinSAFE Logic Terminal 2 2 0 2017 05 10 Version Date...
Page 2: ......
Page 34: ...Operation EL6900 34 Version 2 2 0 Fig 18 Creating a TwinSAFE group...
Page 37: ...Operation EL6900 37 Version 2 2 0 Fig 22 Appended Emergency Stop block...
Page 59: ...Appendix EL6900 59 Version 2 2 0 5 2 Certificates...