EL2911 process image
The process image of the EL2911 consists 6 bytes of process data in the input and the output.
Fig. 28: EL2911 process image
The assignment of the individual signals in the safe data is listed in the following table.
Name
Process
image
Bit position Description
FSOUT Module.Module Fault
IN
0.0
Module error information for safe output
FSIN
Channel1.Channel1.Input
IN
0.1
Safe input channel 1
FSIN
Channel2.Channel1.Input
IN
0.2
Safe input channel 2
FSIN Module.Channel3.Input
IN
0.3
Safe input channel 3
FSIN Module.Channel4.Input
IN
0.4
Safe input channel 4
FSIN Module.Module Fault
IN
0.5
Module error information for safe input module
FSOUT Module Output
OUT
0.0
Safe output to power contact
FSOUT Module.ErrAck
OUT
0.1
Error acknowledge for safe output module
FSIN Module.ErrAck
OUT
0.2
Error acknowledge for safe input module