![Beckhoff EK9500 Documentation Download Page 40](http://html1.mh-extra.com/html/beckhoff/ek9500/ek9500_documentation_2719251040.webp)
Configuration
EK9500
40
Version: 1.0.0
Sample configuration with EPxxxx EtherCAT Box
Fig. 33: Sample configuration with EPxxxx EtherCAT Box
Sample configuration with EK1122 2-port EtherCAT junction
The counting direction is to be observed when using an EK1122.
If EtherCAT junction 1 on the EK1122 is connected, then the EtherCAT frame is forwarded here first (1); if
junction 1 is not connected the frame on junction 2 is sent (2), only after that does the sequence continue
with the E-bus on the right-hand side (3).
Fig. 34: Sample configuration with EK1122 2-port EtherCAT junction
If neither junction is used, then junctions 1 and 2 are bridged, so to speak, and the EtherCAT frame goes
directly to the E-Bus on the right-hand side.