![Beckhoff EK9500 Documentation Download Page 28](http://html1.mh-extra.com/html/beckhoff/ek9500/ek9500_documentation_2719251028.webp)
Parameterization and commissioning
EK9500
28
Version: 1.0.0
4
Parameterization and commissioning
4.1
Further interfaces
Additional interfaces are located under the flap of the EK9xx0.
Fig. 20: Additional interfaces of the EK9xx0
Battery
No battery is required for the EK9xx0, therefore this option is not included.
Red DIP switch
Default setting is OFF/OFF.
In order, for example, to load new firmware to the EK via USB, the first DIP switch must be set to “1” before
switching on. If the RUN LED lights up blue, the EK can be connected to the PC by a USB cable. The PC
then finds the internal Flash as the storage medium. The storage medium may not be formatted!
Micro SD card
Alternatively the firmware can also be loaded to an SD card. Booting always takes place from the SD card if
there is one in the slot. This can be used, for example, to test a firmware before copying it to the EK’s
internal Flash.
USB interface
The USB interface can only be used if the “red” DIP switch has been set accordingly. See “Red DIP switch”.
4.2
IP address
The IP address or the mode (e.g. DHCP) can be set using the DIP switch. Furthermore, an HTML page is
available for the configuration.
4.3
DIP switch
Ten-pole DIP switch S001
The DIP switch has the following meaning for the Ethernet interfaces X001 and X002, which are switched:
Summary of Contents for EK9500