Operation
EK1960
86
Version: 1.3.1
Fig. 101: User Administration - New User added
Several users can be created before leaving the dialog via the
Finish
button.
Access Rights
Description
Change Password
Users can change their password.
Download Safe Logic Data
The user can load the safety-related program onto the EL6910, EJ6910 or
EK1960.
Download Mapping Data
The user can load the mapping data for inputs, outputs, FBs etc. onto the
EL6910, EJ6910 or EK1960.
Download Safe User Data /
Replacement Values
The user can change safe user parameters on the EL6910, EJ6910 or
EK1960 and also change and load safe substitute values
Download Info Data
The user can activate and load the info data for connections and FBs on
the EL6910, EJ6910 or EK1960.
Download Project Data in
Restore Mode
The user can perform a restore. Not currently supported.
Activate / Deactivate Groups
The user can execute Customizing (enable and disable TwinSAFE groups)
on the EL6910, EJ6910 or EK1960.
4.7
Backup/Restore
Following the exchange of an EL6910, EJ6910 or EK1960, the previous project can be loaded to the new
device using the
Backup/Restore
mechanism.
In order to be able to use this functionality, the
Backup/Restore
mechanism must be enabled in the safety
project, and the terminals must be selected, on which the current CRC of the safety project is to be stored.
For a restore operation the user can specify the minimum number of selected terminals on which the correct
CRC must be stored.
Using the checkbox
Restore User Administration
the user can specify whether the user administration should
be transferred to the new device via the restore mechanism.
Summary of Contents for EK1960 Series
Page 1: ...Operating Instructions for EK1960 TwinSAFE Compact Controller 1 3 1 2019 01 28 Version Date...
Page 2: ......
Page 6: ...Table of contents EK1960 6 Version 1 3 1...
Page 58: ...Operation EK1960 58 Version 1 3 1 Fig 51 Safety parameters of the input modules...
Page 140: ...Appendix EK1960 140 Version 1 3 1 5 2 Certificates...