Product overview
EK110x, EK15xx
26
Version: 3.6
• if the EtherCAT master supports HotConnect, then an I/O group can be adopted dynamically into the
EtherCAT communication. This group can then be located at any position within the EtherCAT network.
Variable topologies are therefore easily implementable.
Quick links
•
EtherCAT basics [
}
31]
•
Application notes [
}
56]
•
Diagnostic LEDs [
}
66]
2.4.1.2
EK1501 - Technical data
Technical data
EK1501
Task within the EtherCAT system
Coupling of EtherCAT Terminals (ELxxxx) to
100BASE-FX EtherCAT networks
Number of EtherCAT Terminals
up to 65535 in the overall system
Number of peripheral signals
max. 4.2 GB addressable IO points
Transmission medium
Multimode glass fiber (MM)
Cable length between two Bus Couplers
max. 2 km (100BASE-FX)
Transceiver wavelength
typically 1300 nm
Protocol / Baud rate
EtherCAT Device Protocol / 100 MBaud
HotConnect
max. number of configurable IDs: 4096
Delay
typical 1 µs
Bus connection
2 x SC Duplex
Power supply
24 V
DC
(-15%/+20%)
Current consumption
130 mA + (E-bus current)/4
E-bus power supply (5 V)
depending on ambient temperature
(at higher current consumption the
EL9410
power
feed terminal can be used in addition)
max. 2000 mA (-25°C ... +55°C)
max. 1000 mA (> +55°C)
Power contacts
max. 24 V
DC
, max. 10 A
Electrical isolation
500 V (power contact/supply voltage/EtherCAT)
Dimensions (W x H x D)
approx. 49 mm x 100 mm x 70 mm
Weight
approx. 190 g
Permissible ambient temperature range during
operation
-25°C ... +60°C (extended temperature range)
Permissible ambient temperature range during
storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Mounting [
}
37]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
ATEX [
}
54]
cULus [
}