background image

 

Appendix 

 

C33xx 

29 

Appendix 

 

Technical data

 

Industrial-PC C3320 

Dimensions (W x H x D):

 

482.7 x 355 x 282 mm 

Weight:

 

18 kg (basic configuration) 

Industrial-PC C3330 

Dimensions (W x H x D):

 

482.7 x 400 x 282 mm 

Weight:

 

18,5 kg (basic configuration) 

Industrial-PC C3340 

Dimensions (W x H x D):

 

482.7 x 355 x 282 mm 

Weight:

 

18,5 kg (basic configuration) 

Industrial-PC C3350 

Dimensions (W x H x D):

 

482.7 x 444 x 282 mm 

Weight:

 

19 kg (basic configuration) 

Do not use the PC in areas 
of explosive hazard 

The Industrial PC may not be used in areas of explosive hazard. 

 

 

The following conditions must be observed during operation: 

Environmental conditions 

Ambient temperature:

  

0 to 55°C 

Atmospheric humidity:

 

Maximum 95%, non-condensing 

Shock resistance 

Sinusoidal vibration: 

 

(EN 60068-2-6)

 

10 to 58 Hz:

 

0.035 mm 

 

58 to 500 Hz:  0.5 G (~ 5 m/ s

2

)   

During reading of CD-ROM:

 

10 to 58 Hz:

 

0.019 mm  

 

58 to 500 Hz:  0.25 G (~ 2.5 m/ s

2

Impact: 
(EN 60068-2-27)

 

5 G (~ 50 m/ s²), duration: 30 ms 

During reading of CD-ROM:

 

5 G (~ 50 m/ s²), duration: 11 ms 

Protection class 

Protection class:

 

IP 65 (front side), IP20 (back side) 

 

Power supply 

100-240 V

AC

 power pack 

Supply voltage:

 

100-240 V 50-60 Hz 

Power consumption:

 

100 W for the basic version 

 

Power supply 24 V

DC

  

power pack (optional) 

Supply voltage:

 

22 

– 30 V

DC

 

Power consumption:

 

100 W for the basic version 

 

Electromagnetic 
Compatibility (EMC) 

Interference resistance:

 

according to EN 61000-6-2

  

Emitted resistance:

 

according to EN 61000-6-4 

Transport and storage 

The same values for atmospheric humidity and shock resistance are to be 
observed during transport and storage as in operation. The shock 
resistance during transport can be improved by means of suitably packing 
the Industrial PC. The ambient temperature during storage and transport 
must be between -20°C and +65°C. 

i

 

Note 

Pixel errors in the TFT display are production-caused and represent 
no complaint-reason! 

 

 

Approvals

 

 

FCC: Federal Communications Commission 
Radio Frequency Interference Statement 

FCC Approval for USA 

This equipment has been tested and found to comply with the limits for a 
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection against harmful interference 
when the equipment is operated in a commercial environment. This 
equipment generates, uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the instruction manual, may 
cause harmful interference to radio communications. Operation of this 
equipment in a residential area is likely to cause harmful interference in 
which case the user will be required to correct the interference at his own 
expense. 

 

FCC: Canadian Notice 

FCC Approval for Canada 

This equipment does not exceed the Class A limits for radiated emissions 
as described in the Radio Interference Regulations of the Canadian 
Department of Communications. 

 

Summary of Contents for C33-0060 Series

Page 1: ...Installation and Operating instructions for Build in Industrial PC C33xx from 0060 Version 3 0 Date 2020 04 23...

Page 2: ......

Page 3: ...cabinet 12 Earthing measures 12 Power Supply Connection 13 Current carrying capacity of the 100 240 V power supply unit 13 Current carrying capacity of the 24 V power supply unit 13 Differently coded...

Page 4: ...Foreword 2 C33xx 6 Assembly dimensions 25 7 Appendix 29 Technical data 29 Approvals 29 FCC Federal Communications Commission Radio Frequency Interference Statement 29 FCC Canadian Notice 29...

Page 5: ...nSAFE and XFC are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes coul...

Page 6: ...ded to alert the reader to the associated safety instructions Danger This symbol is intended to highlight risks for the life or health of personnel Warning This symbol is intended to highlight risks f...

Page 7: ...ent must first be switched off after which the Industrial PC can be uncoupled from the plant Pulling out the fieldbus connection plug uncouples the PC optional Items of equipment that have been switch...

Page 8: ...le National regulations depending on the machine type Depending on the type of machine and plant in which the Industrial PC is being used there will be national regulations for the control of such mac...

Page 9: ...EDs a reset button and a further lock for opening the front cover are located Lock for opening the front flap see arrow When the front flap has been unlocked it can be folded upwards Front view of the...

Page 10: ...hind the front door 1 is a 7 slot computer core with standard ATX motherboard 2 and power supply unit 3 Removing the drives The drives 1 2 can be removed without using any tool After removing the card...

Page 11: ...tion shows the assembly of the PC 1 with excerpt frameworks 2 and telescope rails 3 The interface connections are at the side of the housing 4 Connections behind the front flap The connections for the...

Page 12: ...13 allow the PC to be connected to a 10 100 1000BASE T Local Area Network LAN DVI D Digital Visual Interface DVI out The DVI connectors X114 X115 are used for transferring the video signal DVI D stand...

Page 13: ...riations in temperature make sure that moisture condensation does not form on or inside the device Prior to operation the unit must be allowed to slowly adjust to room temperature Should condensation...

Page 14: ...way that reflections on the screen are avoided as far as possible Use the position of the screen as a guide for the correct installation height it should be optimally visible for the user at all times...

Page 15: ...Supplied mains power unit The Industrial PC is either fitted with a 100 240 V 50 60 Hz power supply unit standard or with a 24 VDC power supply unit with the option of an uninterruptible power supply...

Page 16: ...a snap on strain relief housing in order to assemble the PC power supply cable Materials for assembly of the connector Female plug connector Strain relief housing Female plug connector is correspondi...

Page 17: ...switch Pin Funktion 1 Power Status 2 PC_ON 3 24 VDC Versorgungsspannung Pol Pin Function 1 24V DC Power supply 2 3 4 not used 5 not used Fitting the connector to the cable The plug is fitted to the ca...

Page 18: ...24 V via a switch the PC shuts down according to the rules The PC_ON signal is inverted i e the PC shuts down if the 24 V connection is live If the PC_ON input is NOT connected by the user the PC can...

Page 19: ...agram external switch and power supply Wiring diagram Wiring according to the wiring diagram the circuit of PC_ON and Power Status is symbolical Connection of the Battery Pack and UPS Output only in c...

Page 20: ...Industrial PC and to the devices that are to be connected Connect all data transfer cables if present to the appropriate plug in receptacles of the data telecommunication networks Reconnect all device...

Page 21: ...that the probability of causing damage by switching off while the software is running is very high Warning When you have shut down the Industrial PC you have to switch off power supply for at least 10...

Page 22: ...keys of a Microsoft mouse Del The Del key deletes the character to the right of the cursor Ins The Ins key causes characters to the right of the cursor to be overwritten The overwrite mode is cancelle...

Page 23: ...Function keys F 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8 F 9 F 1 0 F 1 1 F 1 2 The meaning of the function keys F1 to F10 is determined by the software and is displayed at the bottom edge of the display Special...

Page 24: ...th the identical type or an alternative type recommended by the manufacturer Notice correct polarity Danger Handling of Lithium Batteries Lithium Batteries should not be recharged exposed to fire open...

Page 25: ...gs are incorrect Other cause Remove floppy disk or CD and press any key Check the setup settings Call Beckhoff Service Computer boots software starts but control does not operate correctly Cause of th...

Page 26: ...lshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Web http www beckhoff de Beckhoff Support Beckhoff offers you comprehensive technical assistance h...

Page 27: ...ams of the Industrial PCs with dimensions in mm Warning The assembly of the unit must take place with the orientation diagrammed here Industrial PC C3320 front view side view plan view cut out for ins...

Page 28: ...with the orientation diagrammed here Industrial PC C3330 front view side view plan view cut out for installation side view with excerpt frame for front assembly through hole for M4 screws screw mounti...

Page 29: ...with the orientation diagrammed here Industrial PC C3340 front view side view plan view cut out for installation side view with excerpt frame for front assembly through hole for M4 screws screw mounti...

Page 30: ...with the orientation diagrammed here Industrial PC C3350 front view side view plan view cut out for installation side view with excerpt frame for front assembly screw mounting M3x10 through hole for M...

Page 31: ...Interference resistance according to EN 61000 6 2 Emitted resistance according to EN 61000 6 4 Transport and storage The same values for atmospheric humidity and shock resistance are to be observed du...

Reviews: