Segment Protector for Cabinet
Installation
R2-SP-N*
<
4 ... 12 outputs Ex ic, Ex nL (FISCO or Entity) or non-incendive
(Div 2)
<
Short circuit current limitation per output
<
Segment Protector in Zone 2/Div. 2
<
Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
<
For FOUNDATION Fieldbus H1 and PROFIBUS PA
<
Power, Com, and Error LEDs
<
T-connector for easy installation and maintenance
<
Test points for easy troubleshooting
Function
The R2 Segment Protector, a device coupler for DIN rail installation, connects 4 ... 12 instruments located in Zone 2/Div. 2. to the segment with
intrinsic safety (Ex ic), energy limitation (Ex nL). Device connections in Zone 1/Div. 1 require additional methods of ignition protection. Short circuit
protection at each spur ensures proper operation of the segment during faults or hot work at the spur.
The T-connector at the trunk allows for exchange of a Segment Protector with no effect on the remaining segment. The terminator is mounted at
the 'T' and removed for network extensions ensuring proper termination.
All plugs feature retaining screws. LEDs and test access points simplify troubleshooting and help to decrease repair time. Any grounding and
shielding concept is possible based on FieldConnex enclosure solutions.
Connection
T
I
I
Spur
Trunk,
Ex nA
non-arcing
Spur
I
I
Spur
Spur
Spur 1 ... n
Ex ic, Ex nL
Zone 2/Div. 2
-
S
+
-
S
+
-
+
S
-
+
S
-
S
+
Technical Data
Fieldbus connection
Main cable (Trunk)
Rated voltage
9 ... 31 V DC
Rated current
max. 4.5 A
Outputs
Number of outputs
see table "Technical data depending on model"
Rated voltage
max. 31 V
Rated current
max. 43 mA
Short-circuit current
max. 58 mA
Self current consumption
see table "Technical data depending on model"
1
Release
da
te:
2022-07-
-
04
Date
of
Release
date:
2022-07-04
Date
of
issue:
2022-07-04
Filename:
t48119_eng.pdf