Mounting and wiring
BK7150
13
Version: 1.0.0
Connection technology
BK7150
Wiring
Cage Clamp® spring-loaded system
Connection cross-section
0.08 mm² ... 2.5 mm², stranded, solid wire, 28 … 14 AWG
Fieldbus connection
CC-Link open style connector
Power contacts
3 spring contacts
Current loading IMAXX
10 A (125 A short circuit)
Rated voltage
24 V
DC
3.1.2
Installation
The Bus Coupler and all the Bus Terminals can be clipped, with a light press, onto a 35 mm mounting rail. A
locking mechanism prevents the individual housings from being pulled off again. For removal from the
mounting rail the orange colored tension strap releases the latching mechanism, allowing the housing to be
pulled off the rail without any force.
Fig. 3: Release the locking mechanism by pulling the orange tab
Up to 64 Bus Terminals can be attached to the Bus Coupler on the right hand side. When plugging the
components together, be sure to assemble the housings with groove and tongue against each other. A
properly working connection cannot be made by pushing the housings together on the mounting rail. When
correctly assembled, no significant gap can be seen between the attached housings.
Fig. 4: Power contact on the left
Attention
Bus Terminals should only be pulled or plugged in switched-off state.
Insertion and removal of Bus Terminals is only permitted when switched off. The electron-
ics in the Bus Terminals and in the Bus Coupler are protected to a large measure against
damage, but incorrect function and damage cannot be ruled out if they are plugged in un-
der power.