2.3
Technical Data
System data
CC-Link | BK7150
Number of I/O modules
64
Number of I/O points
Depending on controller
Data transfer medium
Shielded 3-core, twisted pair cable
CC-Link Version
1.1
Cable-length
1200 m
900 m
400 m
160 m
100 m
Data transfer rate
156 kbaud
625 kbaud
2.5 Mbaud
5 Mbaud
10 Mbaud
Technical data
BK7150
Number of Bus Terminals
64 (255 with K-bus extension)
Max. number of bytes fieldbus
32 bytes input and 32 bytes output
Digital peripheral signals
112 inputs/outputs
Analog peripheral signals
16 inputs/outputs
Baud rates
156 kbaud … 10 Mbaud
Configuration possibility
Via KS2000 software
Bus Connection
1 x open style connector, 5-pin, included
Power Supply
24 V
DC
(-15%/+20%)
Input current
70 mA + (total K-bus current)/4, 500 mA max.
Starting current
2.5 x continuous current
Recommended fuse
≤ 10 A
K-bus power supply up to
1000 mA
Power contact voltage
24 V
DC
max.
Power contact current load
10 A max.
Dielectric strength
500 V (power contact/supply voltage/fieldbus)
Weight approx.
100 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27/29
EMC resistance burst/ESD
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.
IP 20/variable
Ordering information
Description
BK7150
CC-Link “Compact” Bus Coupler for up to 64 Bus Terminals (255 with K-bus
extension)