Mounting and wiring
BC8050 und BC8150
21
Version: 3.0.0
Power contacts
On the right hand face of the Bus Terminal Controller there are three spring contacts for the power contact
connections. The spring contacts are hidden in slots so that they cannot be accidentally touched. By
attaching a Bus Terminal the blade contacts on the left hand side of the Bus Terminal are connected to the
spring contacts. The tongue and groove guides on the top and bottom of the Bus Terminal Controllers and of
the Bus Terminals guarantees that the power contacts mate securely.
3.2.3
Programming cable
Use the KS2000-Z2 programming cable for serial programming of the Bus Terminal Controller. This cable is
included in the scope of supply of the KS2000 software, or it can be ordered separately (order identifier
KS2000-Z2).
Fig. 11: Programming cable KS2000-Z2
KS2000-Z2
The programming cable offers the option of programming the BCxx50 via the serial interface.
Attention
Do not interrupt the ground connection for the supply voltage
When the programming cable (between BCxx50 and PC) is connected, the ground connec-
tion of the Bus Terminal controller must not be interrupted or disconnected, since this may
destroy the programming cable.