Parameterization and Commissioning
BC5250
47
Version: 2.0.0
K-Bus variables
PLC interface:
Not supported (only included for moving CX or BX projects)
K-bus state:
see Diagnostics
4.2.9
PLC
4.2.9.1
Inserting a PLC project
For variable mapping, configuration has to be specified in the system manager. This is where the link
between PLC and hardware is specified. The variables can process and link bit, byte, word or data
structures. Automatic addressing via the System Manager is possible, but should be checked for offset.
Note
Word alignment, byte orientation
With data structures, ensure that the Bus Terminal Controller saves the data in word align-
ment and the System Manager operates byte-oriented (see
)
A valid project has to be compiled and saved in PLC Control. These data are saved as a *.tpy file. For
inserting a PLC project, right-click on
PLC - Configuration
. Select your current PLC project.
Fig. 43: Selecting the PLC project
Link the PLC variable with the hardware (e.g. digital Bus Terminal).