background image

Instruction Manual

 – Model AFG Oil Burner

4

Inspect/prepare installation site

Chimney or vent

Inspect the chimney or vent, making sure it is properly sized and in good
condition for use.

For those installations not requiring a chimney, such as through-the-wall vented
appliances, follow the instructions given by the appliance and power venter (if
used) manufacturers.

Direct air supply and sidewall venting

Some AFG burners are equipped with combustion air boots to allow use of
outside air for combustion.

When sidewall venting appliances, carefully follow appliance and power venter
instructions for installation and wiring.

Combustion air supply

See NFPA Standard 31 for complete details.

If the burner is not supplied with a reliable combustion air source,

the burner cannot properly burn the fuel. This would result in incomplete com-
bustion, causing sooting and possible emission of carbon monoxide. Severe
personal injury, death or substantial property damage could occur.

Appliance located in confined space

The confined space should have two (2) permanent openings: one near the top
of the enclosure and one near the bottom of the enclosure. Each opening shall
have a free area of not less than (1) one square inch per 1,000 BTU’s per hour
of the total input rating of all appliances within the enclosure. The openings shall
have free access to the building interior, which should have adequate infiltration
from the outside.

Exhaust fans and other air-using devices

Size air openings large enough to allow for all air-using devices in addition to the
minimum area required for combustion air. If there is any possibility of the
equipment room developing negative pressure (because of exhaust fans or
clothes dryers, for example), either pipe combustion air directly to the burner or
provide a sealed enclosure for the burner and supply it with its own combustion
air supply.

Outside air kit applications

Refer to separate instruction sheet supplied with AFG outside air kit for installation.
This optional kit allows combustion air to be piped directly to the burner. (Part
number 51747.)

You must install the outside air kit strictly following the kit instal-

lation instructions. Do not attempt to install outside air piping without using the
AFG outside air kit and instructions. Failure to do so could result in burner or
heating appliance failure, causing potential severe personal injury, death or sub-
stantial property damage.

Prepare burner & site

Table 2

 —

Minimum combustion chamber dimensions

Clearances to burner and appliance

Provide space around burner and appliance for easy service and mainte-
nance.

Check minimum clearances against those shown by the appliance manufac-
turer and by applicable building codes.

Combustion chamber — Burner retrofitting

Verify that the appliance combustion chamber provides at least the minimum
dimensions given in Table 2.

When retrofitting an appliance that has a stainless steel chamber

— A chamber burnout could result from the use of a high performance burner.
Protect the chamber from high temperatures through the use of "wet-pac" or a
similar ceramic liner. Some new equipment may contain stainless steel cham-
bers that have been designed and tested by the manufacturer for use with flame
retention burners — ceramic protection would not be necessary. Refer to appli-
ance manufacturer’s instructions. Failure to comply could result in damage to
heating equipment.

Inspect/prepare installation site 

(continued)

Summary of Contents for 120 Vac/60 Hz

Page 1: ...Types F M air tubes Motor voltage 120 Vac 60 Hz MODEL Oil Burner Instruction Manual AFG AFG AFG burner with type F air tube Type M air tube combinations Type L1 head Type V1 head...

Page 2: ...Prepare burner 5 Check adjust Z dimension 6 Set head position adjusting plate V1 head only 7 Adjust pipe wire burner Mount burner on appliance 8 Connect fuel lines 8 Wire burner 8 Startup adjust burn...

Page 3: ...notify the carrier at once and file the appropriate claim When contacting Beckett for service information Please record the burner serial number and have available when calling or writing You will fin...

Page 4: ...f the equipment room developing negative pressure because of exhaust fans or clothes dryers for example either pipe combustion air directly to the burner or provide a sealed enclosure for the burner a...

Page 5: ...the appliance manufacturer s instructions or the Beckett OEM Specification Guide part number 6711 Do not omit the LFRB when specified Omitting the baffle when specified or installing the baffle when...

Page 6: ...e nozzle line See Figure 2 Loosen the splined nut from the nozzle line Loosen the hex head screw securing the escutcheon plate to the burner housing Place the end of a ruler at the face of the nozzle...

Page 7: ...be installed Even if factory set verify that the Z dimension has not been changed 2 Use the following procedure to adjust the Z dimension if it is not correct Turn off power to the burner Disconnect t...

Page 8: ...ut the bypass plug installed You must install this plug on two pipe oil systems DO NOT install the plug in the fuel unit if connected to a one pipe oil system Failure to comply could cause fuel unit s...

Page 9: ...4G or equivalent primary control Figure 7 Typical wiring R7184 primary control R7184P shown Adjust pipe wire burner Electrical shock hazard Disconnect power before servicing Electrical shock hazard Di...

Page 10: ...ial If motor is not permanently lubricated oil motor with a few drops of SAE 20 nondetergent oil at each oil hole DO NOT over oil motor Excessive oiling can cause motor failure Check motor current The...

Page 11: ...Instruction Manual Model AFG Oil Burner 11 Replacement parts Awaiting new info Service maintain burner...

Page 12: ...d maintenance Properly installed and maintained your AFG burner will provide years of effi cient trouble free operation Please take care of your equipment by following the warnings provided and by doi...

Reviews: