background image

 

75.5911.02 20180226 

 

Page 5 of 9 

 

Master and Slave Module Jumper Settings:

  Prior to power-on, all jumper settings on the Master and Slave boards should be set 

according to the installation.

 

 
Jumper settings include: 

§

  Function J1:  Background Analysis (Master and Slave boards)  

§

  Function J2:  Relay Mode (NO / NC) (Master board only) 

§

  Function J3:  Monitoring Mode (Master board only) 

§

  Function J4:  Master Only or Master and Slave Configuration (Master and Slave boards) 

 

1. 

Jumper J1 (Background Analysis) is a 3-pin configuration located on each module.  Background Analysis is the ability to analyze the background 
in the area of the detection field, to help reduce chances of non-detection due to faulty environmental situations. When ON, Background Analysis 
allows constant detection in the event of one or more of the following situations: 

o

 

Module aimed too high 

o

 

Module incorrectly oriented (towards sky, for example) 

o

 

Defective amplification chain 

o

 

Faulty infrared transmitter 

o

 

Not enough reflectivity off of floor surface 

NOTE:  Floor must have at least 5% reflectivity to allow Background Analysis to function properly. 

 
This configuration greatly reduces the chance of allowing the modules to function less than optimally.  If one of the above-stated faults exists, 
the detector will remain active, thereby causing the door to stay open or to not open.  This fail-safe operation will cause the door to be inoperative 
in the automatic mode, since there will be a constant signal either to the safety input or to the activation input of the door control, depending on 
which module is sensing detection.  If an extremely IR-absorbent floor is present, set J1 to Background Analysis mode. 

 The J1 function must 

be set on each module.

 

 

 

 

Background Analysis Mode – 3-Pin Jumper:  

Center pin and left pin are for Normal Mode, center pin and right pin are for Background Analysis 

mode.

 

          

 

2. 

J2 is a two-position jumper (

ON THE MASTER BOARD ONLY

), which enables either a passive or active relay to be selected.  The 

SuperScan-T comes factory-preset with the relay in the ACTIVE MODE. 

 

 

ACTIVE RELAY:  RELAY ENERGIZED WHEN DETECTOR IS AT REST

 

 
ACTIVE RELAY + NC & COM TERMINAL CONNECTION = 

CLOSED CONTACT DURING DETECTION

 

 
 
 
 
 
 

§

 

Use the NC and COM terminals (5 and 6) and leave JP2 at the factory-preset position. 

§

 

LED indication during detection:  Green LED is OFF, red LED is ON 

§

 

Upon power loss, the contact will be closed.  

 

ACTIVE RELAY + NO & COM TERMINAL CONNECTION = 

OPEN CONTACT DURING DETECTION

 

 
 
 
 
 
 

§

 

Use the NO and COM terminals (4 and 6) and leave JP2 at the factory-preset position. 

§

 

LED indication during detection:  Green LED is OFF, red LED is ON 

§

 

Upon power loss, the contact will be open.  

 

View Looking 
Toward P1 

J2 

MECHANICAL 
ADJUSTMENTS  
 
PRIOR TO 
POWER-ON  

J2 

View Looking 
Toward P1 

Summary of Contents for SUPERSCAN-T

Page 1: ...rupts the angle DESCRIPTION SPECIFICATION Power Supply 12 24 VAC VDC 10 Current Consumption Master On 60 mA max Off 30 mA max Slave On 40 mA max Off 30 mA max Inhibit Input 12 24 VAC VDC 10 inhibited when voltage is applied Monitoring Request Input 12 35 VDC required polarity sensitive Min pulse width duration 50 ms Output Interface relay Relay max contact rating is 1A 30v resistive Detection Rang...

Page 2: ...simply pull the tab out away and downward from the extrusion then rotate the module out from extrusion image below right To re install simply reverse the procedure The PCB must first be installed into the adjustment clip then installed into the aluminum extrusion IMPORTANT NOTE The end of the extrusion that is towards the pivot end of a center hung door should be in far enough from the edge of the...

Page 3: ...below Again be sure not to drill through any through bolts or braces within the door A The extension wire going between the terminal blocks should be approximately 18 long and can then be cut back as needed 8 Next a wire passage hole will be required in the door header image below left and also in the jamb tube image below right at approximately the same height as the SuperScan T The wire transfer...

Page 4: ...the opposite end until all mechanical adjustments have been completed Refer to the appendices of this document for various wiring schematics Terminal Explanation of Wiring Connections 1 Test input when used as a monitored sensor positive when utilizing monitoring 2 Ground negative when utilizing monitoring Negative terminal if Input inhibition is used 3 Input inhibition All detection is ignored In...

Page 5: ...tector will remain active thereby causing the door to stay open or to not open This fail safe operation will cause the door to be inoperative in the automatic mode since there will be a constant signal either to the safety input or to the activation input of the door control depending on which module is sensing detection If an extremely IR absorbent floor is present set J1 to Background Analysis m...

Page 6: ...nded for use without Slave modules added to the chain and is for Master only operation The jumper is located at the Output end of the Master module Master only has jumper installed on two pins closest to center of board With jumper J4 installed as shown in the image to the right middle the Master is intended for Slave modules to be added Jumper J4 is also installed on the last Slave module in the ...

Page 7: ... below to help determine the angling The angles may have to be altered once the units have been powered up and walk tested INACTIVE ZONE B DISTANCE FROM FLOOR SUPERSCAN T ANGLE 0º 5º 10º 15º 20º 25º 8 0 6 12 19 26 33 12 0 6 12 18 24 31 16 0 5 11 16 23 29 20 0 5 10 16 21 27 Approach Side Safety Side Hinge Side Leading Edge Side Slave module Master module Door Cord must be placed on interior of door...

Page 8: ...d non monitoring modules in the same chain observe the following rules Non monitoring Master modules CANNOT be used with monitoring Slave modules All other combinations will work however for a system to utilize monitoring all modules must be monitoring modules PROBLEM POSSIBLE CAUSE CORECTIVE ACTION SuperScan T does not work at all No LED indications Faulty power supply Faulty connections Power su...

Page 9: ...mpliance issue is noted The equipment should be inspected annually in accordance with the minimum inspection guidelines A safety check that includes at a minimum the items listed on the safety information label must be performed during each service call If you are not an AAADM certified inspector BEA strongly recommends you have an AAADM certified inspector perform an AAADM inspection and place a ...

Reviews: