75.5911.02 20180226
Page 6 of 9
PASSIVE RELAY: RELAY DE-ENERGIZED WHEN DETECTOR IS AT REST
PASSIVE RELAY + NO & COM TERMINAL CONNECTION =
CLOSED CONTACT DURING DETECTION
§
Use NO and COM terminals (4 and 6) and
CHANGE JP2
from the factory-preset position.
§
LED indication during detection: Green LED is ON, red LED is ON
§
Upon power loss, the contact will be open.
PASSIVE RELAY + NC & COM TERMINAL CONNECTION =
OPEN CONTACT DURING DETECTION
§
Use the NC and COM terminals (5 and 6) and
CHANGE JP2
from the factory-preset position.
§
LED indication during detection: Green LED is ON, red LED is ON
§
Upon power loss, the contact will be closed.
3.
Jumper J3 (located only on Master module) is to toggle the monitoring mode on and off.
§
Monitoring OFF = jumper installed on both pins (image below, left)
§
Monitoring ON = jumper removed (may be stored on one pin) (image below, right)
§
Monitoring is not available on Master modules without jumper J3 installed.
4.
Jumper J4, is found on the Master and Slave modules. On the Master module, it determines ‘Master only’ or ‘Master and Slave’ configuration
for use when Monitoring is ON.
When the jumper is installed in ‘Master only’ configuration (image right, top), it is intended for use without
Slave modules added to the chain and is for ‘Master only’ operation. The jumper is located at the Output
end of the Master module. (‘Master only’ has jumper installed on two pins closest to center of board.)
With jumper J4 installed as shown in the image to the right (middle), the Master is intended for Slave
modules to be added. Jumper J4 is also installed on the last Slave module in the multi-module chain, near
the output end of the module.
As shipped From BEA, Inc., default placement of J4 jumpers is as follows:
§
If a Master ONLY is shipped: Jumper will be positioned for Master Only
§
If a Slave ONLY is shipped: No jumper on Slave J4 position
§
If a kit is shipped (i.e. SuperScan-T II): Jumpers correctly for monitoring in that configuration.
On the Slave module, jumper J4 should be installed on the last Slave module in the chain, as shown in the
image to the right (bottom). All Slave modules between the Master and the last Slave should have the
jumper removed.
There is a hold-time potentiometer (P1) located on the Master module. It is located between the receiver
and transmitter. Adjustability ranges from 0.1 – 4.5 seconds. When installed, clockwise rotation increases
time delay.
J2
View Looking
Toward P1
J4
MECHANICAL
ADJUSTMENTS
PRIOR TO
POWER-ON (cont.)
J2
View Looking
Toward P1
J4
View Looking Toward
Master Output
J4
View Looking Toward
Master Output