Installation height > 4m, the test body CA (EN16005) might not be detected.
Use the remote control to define the left width C and the right width A, then launch an environment learn.
( + + ) . LED goes off after finishing the environment learning process. No need to define the
width of the field with your hand in this mode.
DETECTION ZONE SETTING & TEACH-IN
Set the detection range either automatically or with the remote control:
1.
To launch a teach-in, press 2 seconds the push button by remote control ( + + ).
The sensor starts flashing red-green quickly and automatically learns the installation height. (Please make
sure to stand outside the detection field before starting the teach-in process.)
2.
Wait until the sensor flashes green. Stretch out your arm in front of you and make an up and down
movement to define the left/right limit of the detection field. The LED flashes red while calculating.
3.
Wait until the sensor flashes green again. Stretch out your arm in front of you and make an up and down
movement to define the right/left limit of the detection field. The LED flashes red while calculating.
4.
Once the LED is off, the teach-in is complete.
With the remote control
Left
detection
area
Safety field teach-in
Virtual push button teach-in
1.
To launch a teach-in by remote control ( + + ). The sensor starts flashing red-green
quickly and automatically learns the environment. (Please make sure to stand outside the detection field
before starting the teach-in process.)
2.
Wait until the sensor flashes green. Put your hand in front of the first virtual push button and keep until the
red LED flashes. Move away from your hand when the red LED flashes.
3.
Wait until the sensor flashes green again. Put your hand in front of the second virtual push button and keep
until the red LED flashes. Move away from your hand when the red LED flashes.
4.
Once the LED is off, the two virtual push button teach-in is complete.