SYMPTOM 

PROBABLE CAUSE 

CORRECTIVE ACTION 

The door will not open and 
no red LED lights up. 

The sensor power is off. 

Check the wiring and the power supply. 

The sensor "sees" the door moving. 

Increase the tilt angle and/or reduce the sensitivity. 

The door opens and closes 
constantly. 

When closing the door creates vibrations 
picked up by the sensor. 

Ensure that the sensor is correctly fixed. 
If the rejection mode is set at level 1, set this parameter to 
level 2. 
Reduce the sensitivity. 
Switch to unidirectional mode. 

The sensor will not unlock 
when access code is 
entered. 

Improper access code being entered. 

Cut and restore power supply. No access code is required 
to unlock during the first minute after powering. Press on 
“unlock”, then on “lock” and introduce a new access code. 

Batteries in the remote control are weak 
or installed improperly. 
 

Check the batteries insertion. 
Change the batteries. 

The sensor does not 
respond to the remote 
control. 

Remote control is badly pointed. 

Point the remote control towards to the sensor. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
TROUBLE-
SHOOTING 

 

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a 
problem, please call B.E.A., Inc.  If you must wait for the following workday to call B.E.A., leave the door 
inoperable until satisfactory repairs can be made.   Never sacrifice the safe operation of the automatic door 
or gate for an incomplete solution. 

 

 

 

The following numbers can be called 24 hours a day, 7 days a week.  For more information, visit 

www.beasensors.com

.   

 

 
 
 

West: 1-888-419-2564 

Mid-West: 1-888-308-8843 

South-East: 1-800-407-4545

 

North-East: 1-866-836-1863 

US and Canada: 1-866-249-7937 

Canada: 1-866-836-1863 

 

 

 

 
COMPANY 
CONTACT 

Summary of Contents for FALCON DR

Page 1: ...witching power 30W DC 60VA AC Hold time 0 5s to 9s adjustable Temperature range 22 F to 122 F 30 C to 60 C Degree of protection IP65 Norm conformity R TTE 1999 5 EC EMC 89 336 EEC Dimensions 4 W x 5 D x 3 H 102 mm W x 127 mm D x 96 mm H Weight 0 88 lbs 0 4 kg Material of housing ABS and polycarbonate Material of bracket Anodized aluminium Length of cable 33 10m Manual adjustment Orientation of sen...

Page 2: ...ousing Screw the 2 front cover screws and tighten the retaining nut Check that both locking collars are at the same position Align the bracket slot to the locking collar guide as shown BROWN GREEN Power supply YELLOW COM 1 WHITE NC 1 PINK NO 1 BLACK COM 2 RED NC 2 BLUE NO 2 To insert or to remove the cable Unscrew the retaining nut Pass the cable through the retaining nut and the grommet Screw the...

Page 3: ...ng adjustments Tilt angle 30 Sensitivity 9 6 3 The sensing fields here on the left correspond to the following adjustments Tilt angle 15 30 45 Sensitivity 9 The sensing fields here on the left correspond to the following adjustments Tilt angle 15 30 45 Sensitivity 9 The sensing fields here on the left correspond to the following adjustments Tilt angle 30 Sensitivity 9 6 3 The sensing fields here o...

Page 4: ...NLOCK key 4 Enter your 4 digit access code using 0 9 NUMBER keys 1 During the first sensor adjustment or if the access code is reset to the 0000 value factory setting or during the first minute after the power on press only the UNLOCK key 4 no access code required UNLOCK with access code UNLOCK without access code The red LED flashes quickly waiting for the access code After entering the correct a...

Page 5: ...nterferences with the sensor DETECTION MODE Press the DETECTION MODE key 8 Use the NUMBER keys 1 3 1 to select the required mode Key 1 bidirectional mode Key 2 unidirectional mode Key 3 unidirectional mode with the MTF function DETECTION MODE With the bidirectional mode the approaching and departing target is detected With the unidirectional mode only the approaching target is detected Using the M...

Page 6: ...o the factory values Press and hold both push buttons simultaneously until the two LEDs switch on for 1 second after 2 seconds During the manual adjustment session the red and green LEDs flash successively and continuously The flashing number of the red LED provides the number of the displayed parameter see next table The flashing number of the green LED provides the value of the displayed paramet...

Page 7: ... on unlock then on lock and introduce a new access code Batteries in the remote control are weak or installed improperly Check the batteries insertion Change the batteries The sensor does not respond to the remote control Remote control is badly pointed Point the remote control towards to the sensor TROUBLE SHOOTING Do not leave problems unresolved If a satisfactory solution cannot be achieved aft...

Reviews: