BEA EAGLE ONE HM User Manual Download Page 6

6/8 

During an adjustment session all parameters may be reset to their factory values in the following way :

 

PARAMETERS 

OPERATIONS 

FACTORY 
VALUES 

 

Press the 

SETUP

 key (19), then press the 

NUMBER 

key

 9. 

All the parameters (except the access code) are reset to the factory values.  
 
 

FACTORY VALUES :

 

 

 

 

 

Factory Values Table 

Parameter 

Values 

Factory setting 

Sensitivity 

0 - 9 

Hold time 

0 - 9 

Detection mode 

1 - 5 

2 (EAGLE ONE HM) – 1 (EAGLE TWO HM) 

Immunity 

1 - 9 

Mounting height 

1 - 2 

Output configuration 

1 - 2 

Door control 

1 - 3 

 

 

 

If you do not have a remote control, you can only adjust the sensitivity parameter, by means of the push b and - . 

 

 

 

+

 : press to increase the sensitivity by one unit 

-

 : press to decrease the sensitivity by one unit 

 

 
The factory default values (except the factory value of the access code) may be restored by pressing the two push buttons together for 
at least two seconds. 
 

 

 

The LED flashes for a few seconds after the power-on, and flashes during the 
configuration with the remote control. 
 
The LED lights up when the sensor detects motion. 
 

 

 
 
 

SYMPTOM 

PROBABLE CAUSE 

CORRECTIVE  ACTION 

The door will not open and no red LED 
lights up. 

The sensor power is off. 
 
The door control is set to level 3. 

Check the wiring and the power supply. 
 
Set door control to automatic mode (level 1). 

The sensor "sees" the door 
moving. 

Increase the tilt angle and/or reduce the sensitivity 
and/or increase the immunity. 

The door opens and closes constantly. 

When closing the door creates 
vibrations picked up by the sensor. 

Ensure that the sensor is correctly fixed. 
Switch to unidirectional mode. 
Increase the immunity. 
Reduce the sensitivity. 

The door will not close. 
Red LED OFF 

On-Off switch at door control in 
wrong position or is faulty 
Improper output configuration on 
the sensor. 

Check to insure On-Off switch for door is in the ON or 
AUTOMATIC position.  
Check the output configuration setting on each 
sensor connected to the door operator. 

It rains and the sensor detects for no 
apparent reason. 

The sensor detects the motion of 
the rain drops. 

Use the ERA accessory. 
Switch to unidirectional mode (without MTF) and 
increase the immunity. 

In airlock vestibules, the sensor sees the 
opposite door. 

 

Increase immunity. 

In airlock vestibules, the sensor sees the 
movement of the door leaves, despite of 
an increased immunity. 

 

Make sure that the antenna for the narrow sensing 
field is used. 

In metallic environments, the sensor 
detects objects outside its detection field. 

 

Increase immunity. 

 
SENSITIVITY 
CONFIGURATION 
WITH  PUSH 
BUTTONS 

 
LED SIGNAL 

 
TROUBLE-
SHOOTING 

Summary of Contents for EAGLE ONE HM

Page 1: ... 215 kg Material ABS Color of housing anthracite gray aluminum finish or white Length of cable 2 5m Manual adjustment Sensitivity by push buttons Orientation of sensing field mechanically Remote control adjustments Sensitivity Hold time Detection mode Immunity Mounting height Output configuration Door control Security 10 levels from 0 5s to 9s in 10 levels uni bidirectional MTF reverse mode Eagle ...

Page 2: ...ock 12 24V AC DC COM NO NC This device may be fixed on the ceiling as long as the spherical part of the sensor is facing in the direction opposite the door and as long as an angular position of around 70 is chosen for the antenna For the mounting on the upper part of the door operator profile use the EBA support For a mounting into the ceiling use the ECA embedding support For a better water tight...

Page 3: ...GLE OF THE ANTENNA The sensing fields here on the right correspond to the following adjustments Sensitivity 9 Bidirectional mode Mounting height 5m To obtain a sensing field as close to the door as possible set the antenna at its minimum tilt angle 0 to 15 Example of deep field operator application To obtain a sensing field close to the door set the antenna at a tilt angle of 30 Example of standar...

Page 4: ...e access code can be composed of 1 to 4 digits factory values or no access code 0 or 0000 During the first sensor adjustment or if the access code is reset to the 0000 value factory setting or during the first minute after the power on press only the UNLOCK key 4 no access code required UNLOCK with access code of 4 digits UNLOCK with access code of less than 4 digits UNLOCK without access code The...

Page 5: ... MODE key 8 Use the NUMBER keys 1 5 1 to select the required mode Key 1 Bidirectional mode Key 2 Unidirectional mode Key 3 Unidirectional mode with MTF function Key 4 Unidirectional mode reverse Key 5 Unidirectional mode reverse with MTF function DETECTION MODE With the bidirectional mode the approaching and departing target is detected With the unidirectional mode only the approaching target is d...

Page 6: ...or control is set to level 3 Check the wiring and the power supply Set door control to automatic mode level 1 The sensor sees the door moving Increase the tilt angle and or reduce the sensitivity and or increase the immunity The door opens and closes constantly When closing the door creates vibrations picked up by the sensor Ensure that the sensor is correctly fixed Switch to unidirectional mode I...

Page 7: ...ck during the first minute after powering Press on unlock then on lock and introduce a new access code Batteries in the remote control are weak or installed improperly Check the batteries insertion Change the batteries The sensor does not respond to the remote control Remote control badly pointed Point the remote control towards the sensor TROUBLE SHOOTING ...

Page 8: ...ion of conformity and other technical documentation are available on our website or can be requested by phone or mail BEA S A LIEGE Science Park Allée des Noisetiers 5 B 4031 Angleur Tel 3243616565 Fax 3243612858 info bea be www bea be ...

Reviews: