background image

75.5501.02  EN   20091102   (75.5500)   

 

 

 

 

 

 

 

 

Page 6 of 15

  The LE22 function provides a sequence for Relay 1 and/or Relay 

2 with an inhibitor of activation for Input 1 until Input 2, Input 

3 or ‘WET’ Input is triggered, which all activate the sequence.  

Additionally Input 4 provides a door position switch input for 

which closing it will re-inhibit Input 1.  Simply put this function is a 

combination between a LE21 and MC25.  Adjustable parameters 

include 

H1

 for activation hold time of Relay 1, 

H2

 for activation 

hold time of Relay 2 and 

D1

 for delay between activation of 

Relay 1 to Relay 2.  A re-activation of the sequence before it 

expires will re-start both hold timers and keep the relays active. A 

maintained input will freeze both hold timers, thus keeping their 

relays active until the input is released, which will allow the hold 

timers to expire and deactivate the relays normally.

 

NOTE

:  The delay timer will only fire one time during 

initial activation or maintained input.

 

NOTE:  The door position switch must have a closed 

contact when the door is closed and an opened 

contact when it is not.

A typical application is a ‘Low-Energy’ situation, which needs 

security, in which you have only ‘Knowing-Act’ activation 

devices such as push-plates and a re-activation device, such 

as a SuperScan, on the door for safety and a door position 

swtich.   For this scenario the push-plates would be wired to 

Inputs 2 and/or 3, the SuperScan would be wired to Input 1, 

a door position switch on Input 4, a security device such as a 

Maglock or electric strike on Relay 1 and the door controller on 

Relay 2.  When the door position switch on Input 4 is closed,

the SuperScan input is ignored (inhibited) and only becomes a re-activation device (uninhibited) after an activation on Input 2 or Input 3. The 

SuperScan on Input 1 will remain uninhibited until the door is closed again closing Input 4.  An example wiring diagram for this scenario is shown.

NOTE:  While the ‘WET’ Input is not involved in our typical application, it will still function as Input 2 and Input 3 do if used.

LE22 SETUP

1.  Wire the Br3 accordingly.

2.  Select the LE22 as the function according to the steps outlined in Section 5 – Selecting the Function.

•  Press and hold both push buttons (INCR & PARAM) for three (3) seconds to activate the display.

•  Press the INCR button to toggle through each function and select 

22

.

3.  Set the LE22 parameters according to the steps outlined in Section 5 – Selecting the Function.  

•  Press PARAM button to cycle through and set the parameters.

•  Press the INCR button to increment the parameter’s value.

Parameters for the LE22 function are shown in the chart.  Set the parameters as needed for the application and wait for the display to 

become inactive to save the configuration.

PARAMETER

(PARAM Button)

DESCRIPTION

POSSIBLE VALUES

     (INCR Button)

H1

Relay 1 hold time

00

’ through ‘

60

’.  Relay 1 hold time will not begin counting down until the release of Input 1.

H2

Relay 2 hold time

00

’ through ‘

60

’.  Relay 2 hold time will not begin counting down until the delay between 

Relay 1 and Relay 2 expires.

D1

Delay between 

Relay 1 and Relay 2

00

’, ‘_

1

’ (1/4), ‘_

2

’ (1/2), ‘_

3

’ (3/4), ‘

01

’ through ‘

60

’ seconds. The delay time will begin 

counting down with activation of sequence.

4.  Once programming is complete, test the Br3.   Attempt to trigger the sequence via the re-activation device tied to Input 1.  Ensure that 

the sequence does NOT start as it should be inhibited.  The display should still show 

22

 since Relay 1 is de-energized.  Now trigger the 

sequence via Input 2, Input 3 or ‘WET’ Input.  Ensure that the sequence runs and the Relays activate and the timers are as programmed.   

The display will show 

R1

 when Relay 1 is energized, 

R2

 when Relay 2 is energized or 

R=

 when both Relay 1 and Relay 2 are energized at the 

same time.  Before the door closes attempt to re-activate the sequence via the device tied to Input 1.  The door should re-open immediately 

and the relay hold timers should restart.  Once again observe the relay hold times and ensure that it is as programmed.  Let the door close 

and trigger Input 4 via the door position switch.  Once again attempt to trigger the sequence via the re-activation device tied to Input 1.  

Ensure that sequence does NOT start as it should be re-inhibited.

 5. Upon completion of the above steps, walk test the door to ensure all functions, timers, sensors, etc. are working as intended, and that the 

system is in compliance with all applicable standards (i.e. ANSI A156.10, A156.19).

6D   Function 

22

 - 2 Relay Sequence w/Inhibitor (LE22)

G

N

D

IN

-1

G

N

D

IN

-2

G

N

D

IN

-3

G

N

D

IN

-4

1

2

3

4

WET

WET

WET

N

C

N

O

C

O

M

N

C

N

O

C

O

M

12

-2

4V

AC

/D

C

RELAYS

1

2

POWER

RELAY 1

IN

C

R

.

PARAM

SETUP

D

C

AC

D

R

Y

W

ET

INPUTS

2 2

N

C

N

O

C

O

M

3

Br

3

CAUTION:  RELAY 1 WET 

OUTPUT OPTION 

IS ACTIVE FOR 

ALL FUNCTIONS.

12 to 24

 VAC/VDC

+/- 10%

Inputs 2 & 3 can be used for Pushplate 

input or other activation device.

Input 4 is for the door position switch.

Switch is closed when door is closed.

Input 1 for SuperScan

at approach side.

‘WET’ 

12 to 24

 VAC/VDC

+/- 10%

INPUT

+      -

To Activation Circuit 

of Door Control.

Typically Connected to Lock Device.  When DC ‘WET’

Output is Selected for Relay 1, COM Terminal is Positive (+).

Summary of Contents for Br3

Page 1: ...n switch input for which closing it will re inhibit Input 1 Simply put this function is a combination between a LE21 and MC25 6 2 5 MC25 2 Relay Sequence Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input 7 2 8 MC28 2 Relay Sequence w Door Position Input Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input Additionally Input 2 provides a do...

Page 2: ...IPTION SPECIFICATION Supply Voltage 12 to 24 VAC VDC 10 Contact Rating DRY Relay 1 Relay 2 Relay 3 Contact Rating WET Relay 1 3 A at 24 VAC 3 A at 30 VDC 3 A at 24 VAC 3 A at 30 VDC 1 A at 24 VAC 1 A at 30 VDC 1 A Current Consumption 30 to 130 mA DRY Output Temperature Range 15 F 26 C to 150 F 65 C Dimensions 5 2 133mm W x 2 2 55mm D x 1 25mm H Input Specification Inputs 1 to 4 DRY Contact WET Inp...

Page 3: ...long as no relays are active the display will show the function selected otherwise it will show those relays Once the values are changed they are only saved after the display goes inactive again 5 seconds NOTE Remember that the INCR push button always increments the value of the parameter that you are looking at and the PARAM push button toggles through the available parameters NOTE To change only...

Page 4: ...system is in compliance with all applicable standards i e ANSI A156 10 A156 19 75 5501 02 EN 20091102 75 5500 Page 4 of 15 6A Function 10 Timer Module MC10 GND IN 1 GND IN 2 GND IN 3 GND IN 4 1 2 3 4 WET WET WET NC NO COM NC NO COM 12 24V AC DC RELAYS 1 2 POWER RELAY 1 INCR PARAM SETUP DC AC DRY WET INPUTS 1 0 NC NO COM 3 Br3 CAUTION RELAY 1 WET OUTPUT OPTION IS ACTIVE FOR ALL FUNCTIONS 12 to 24 V...

Page 5: ...le parameter for the LE21 function is shown in the chart Set it as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of an activation input 4 Once programming is complete test the Br3 Attemp...

Page 6: ...M button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the LE22 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time wil...

Page 7: ...ding to the steps outlined in Section 5 Selecting the Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC25 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VA...

Page 8: ...ers Press the INCR button to increment the parameter s value Parameters for the MC28 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release o...

Page 9: ...METER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 2 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the delay between Relay 1 and Relay 2 expires D1 Delay between Relay 1 and Relay 2 00 _1 1 4 _2 1 2 _3 3 4 01 through 60 seconds The delay tim...

Page 10: ... application it will still function as Input 1 does if used MC35 SETUP 1 Wire the Br3 accordingly 2 Select the MC35 as the function according to the steps outlined in Section 5 Selecting the Function Press and hold both push buttons INCR PARAM for three 3 seconds to activate the display Press the INCR button to toggle through each function and select 35 3 Set the MC35 parameters according to the s...

Page 11: ...ay to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the release of Input 2 4 Once programming is complete test the Br3 Wait until both doors a...

Page 12: ...set for the MC55 as the state of Relay 1 and Relay 2 are not based on time so just wait for the display to become inactive to save the configuration 4 Once programming is complete test the Br3 Wait until both doors are closed then trigger Relay 1 via Input 1 Ensure that Relay 1 changes state and that is maintained The display will show R1 when Relay 1 is energized Test the interlock by attempting ...

Page 13: ...n to increment the parameter s value Parameters for the MC65 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 for inbound or...

Page 14: ...e Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC75 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 ...

Page 15: ...programmed 3 Jumper an active Input and ensure that the fault is not within the wiring If module works when jumped trace wiring from Inputs relays 4 Replace module Module reacts to input but has no output 1 Wrong outputs are connected 2 Incorrect wiring 3 Incorrect jumper settings 4 Faulty module 1 Check to ensure that the proper outputs are connected per the function selected 2 Trace all wiring t...

Reviews: