background image

Installation Instructions

Pre-Installation Instructions

1.

This product must be installed according to all applicable
building and life safety codes. All installations must be
approved by the Authority Having Jurisdiction (AHJ).

2.

Due to the variety of mounting configurations available with
this product, a survey and assessment of the physical area
in which the product will be installed must be performed. 

3.

The door frame must be inspected and deemed structurally
sound prior to installation of the electromagnetic lock. The
structural integrity of the mounting surfaces must be strong
enough to meet or exceed the holding force of the product. 

4.

The product must be protected from potential damage due
to intruders or tampering. 

5.

The product should be installed in a location that will not
hinder or create a potential safety hazard to authorized
personnel accessing the protected area. 

6.

Because electromagnetic locks are used in a variety of
applications and different door frame configurations, an
experienced installer with knowledge of this product must
make a determination of the optimal mounting method for
this specific application. 

7.

The components, hardware, installation instructions and
mounting template included with this product are intended
for use on outswinging doors. 

8.

Do not install this product on the exterior of buildings. 

9.

Do not use as a doorstop. This will void warranty.

10.

Separate accessories not included with this product must be
used in the following applications: 

• Narrow head jamb situations or center-hung doors 
• Wherever there is insufficient space on the door frame

header to mount the lock

• Hollow metal or wood frames where the door stop is

not thick enough to allow the product to be installed 

• Wherever an obstruction in the door prevents 

installation of the armature plate at a proper height 

• Doors that do not permit the armature plate to be 

mounted low enough to meet the magnet surface 

Refer to the Product Accessories Guide section of the
Installation Instructions for further information. 

11.

Installation of this product should be done by an
experienced installer with knowledge of this product. 

12.

A mechanical latching device is required in conjunction
with the Delayed Egress 10MAGDE1.

NOTE:

It is highly recommended that thread locking compound

be applied to all screws during installation to reduce chance of
screws loosening over extended time.

PLEASE DELIVER ALL INSTALLATION INSTRUCTIONS TO 

THE END-USER UPON COMPLETION OF THE INSTALLATION.

1.

Mount the electromagnetic lock to the door frame as outlined
on the installation template included with the product. 

Armature Plate Mounting Notes: 
1) It is essential that this plate pivot slightly on the mounting bolt
to allow proper alignment with the magnet surface.  If not aligned,
the lock may lose holding force or not lock at all.
2) The rubber washer on the head of the mounting bolt should
project slightly beyond the surface of the armature plate. It will
expand when power is removed and break the air vacuum
between the plate and magnet.  If removed or trimmed, the lock
will appear to have some holding force even when power is
removed.

For added safety, thread locking compound has been provided for

the armature plate bolt and the four captive electromagnetic lock
mounting screws.

WARNING: Improper installation, maintenance, inspection or
usage of the product or any related accessories or parts may
cause the electromagnetic lock, armature plate and associated
hardware to disengage and fall, causing serious bodily injury
and property damage. BEA will not be liable to the installer,
purchaser, end user or anyone else for damage or injury to
person or property due to improper installation, care, storage,
handling, maintenance, inspection, abuse, misuse or act of
God or nature involving this product or any related accessories
or parts.

2.

Route the power supply connecting wire through the door
frame and into the wire access hole in the top of the magnet
housing. Connecting wire should be of sufficient gauge for
the lock being installed and the distance being run. See table
for current draw specifications and wiring gauge chart.

3

.

See system overview and switching options.

Page 1 of 8

Summary of Contents for 10MAGDE1

Page 1: ...ation Instructions for further information 11 Installation of this product should be done by an experienced installer with knowledge of this product 12 A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 NOTE It is highly recommended that thread locking compound be applied to all screws during installation to reduce chance of screws loosening over extended time...

Page 2: ...ssure is maintained for longer than the set nuisance delay an irreversable release delay sequence begins This release delay is for 15 seconds but may be extended to 30 seconds with permission of the Authority Having Jurisdiction AHJ It includes the short nuisance delay Pressure is no longer required on the door The remote relay de energizes The local buzzer changes from a pulse to steady The lock ...

Page 3: ...e overall system with respect to the requirements in the Life Safety Code NFPA 101 for the end use product The Delayed Egress electromagnetic locks are not intended or tested for use as a UL Listed Burglar Alarm System unit Patent Pending MECHANICAL Including 1 4 6 4mm mounting bracket 10MAGDE1 Lock Dimensions 2 1 8 D x 2 7 8 H x 10 13 16 L 54mm x 73mm x 275mm 10MAGDE1 Armature Plate Dimensions 5 ...

Page 4: ... the door a door switch cannot be used for relocking Please connect a momentary spring loaded NORMALLY OPEN key switch to system Reset Switch Input RST 2 STANDARD BUILDING CODE 1999 NUISANCE DELAY Not allowed RELEASE DELAY 15 sec RELOCK Actuates after door OPENS and CLOSES using a door switch rather than a key switch Please connect a NORMALLY OPEN door switch by others to system Reset Switch Input...

Page 5: ...TACT BEA FOR INFORMATION ON A DELAYED EGRESS WITH BUILT IN CAMERA 10MAGDE1 Delayed Egress Electromagnetic Lock Installation Instructions Continued Wiring Diagram Diagram reflects status with power on and door opened A mechanical latching device is required in conjunction with the Delayed Egress 10MAGDE1 Reset and Override Wiring for BOCA Requirements Diagram reflects status with power on and door ...

Page 6: ...s com US and Canada 1 866 249 7937 Canada 1 866 836 1863 Northeast 1 866 836 1863 Southeast 1 800 407 4545 Midwest 1 888 308 8843 West 1 888 419 2564 10MAGDE1 Delayed Egress Series Troubleshooting Guide PROBLEM SOLUTION Remove anti tamper screw and cavity screw Insert supplied Allen wrench into mounting bolt holes in the bottom of the lock housing and turn See Fig 1 Check power supply DC power sho...

Page 7: ... a lock to be installed Available in several different widths For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock from the frame Available in several different thicknesses For use with doors that do not permit the armature plate to be mounted low enough t...

Page 8: ...14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy o...

Reviews: