BEA 10DPHUB User Manual Download Page 16

Appendix C - Home Switch (continued)

Page 

16 

of 

16 

          

75.5652.01 

 

 

20100830

2

Alternative Solutions

  

 

If you cannot use the 

typical

 installation, perhaps due to vertical rods or the customer does not like the look of the Surface Mount Adapter, there

are several alternatives.  All you simply need is to connect a DRY contact switch that is 

closed when the door is closed

.

For example you could use a magnetic bullet switch in the nose of the door with the magnet in the jamb or the other door.  Here you could drill a 

hole through the extrusion and frame and route the wires into the extrusion, then into the EDPS.

Another example would be to use the mechanical limit switch(es) on an equipped operator.  You could install separate wires and route them 

through the door to the EDPS or you could simply splice into the 8-pin connector on one of the EDPS harnesses at the DP-Hub at the 

orange (pin 3) and orange/black (pin 4) wires.  Note that if using the limit switches on a pair of doors, the switches would need 

to be wired in series.

Those are only a 

few

 examples as the possibilities are endless.

NOTE: You only need to connect the alternative solution into 

one

 EDPS or 

one

 EDPS harness.

Magnetic bullet 

switch in the 

nose of the 

door

Mechanical 

limit switch on 

operator

Summary of Contents for 10DPHUB

Page 1: ...rking in public areas Constantly be aware of pedestrian traffic around the door area Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door ESD electrostatic discharge Circuit boards are vulnerable to damage by electrostatic discharge Before handling any board ensure you dissipate your body s ESD charge Always check placement of...

Page 2: ...1 Manual Inhibit INSTALLATION HARNESSES BEA P N 20 5078 02 20 5082 20 5083 20 5222 20 5215 02 20 5096 20 5095 DESCRIPTION ON OFF HOLD Switch Harness BodyGuard Harness BodyGuard Y Harness optional for dual egress pair Door Control Harness Door Mounted EDPS Harness Eagle Harness Power Harness Page 2 of 16 75 5652 01 20100830 2 Install DP Hub 1 Install the DP Hub in an accessible location inside the ...

Page 3: ...r control s as displayed above 2 Route wiring harness s 20 5222 from door control to DP Hub and plug into DP Hub at location marked CONTROL 1 and or CONTROL 2 NOTE Typically on the door control the common COM for the Stall input is isolated from the common for Activation and Safety If the door control has one common input tie all the common outputs from the DP Hub together 1 PWR 2 PWR 3 COM 4 NO 5...

Page 4: ...be obtained or for more precise Home Switch installation please refer to Appendix C 2 Wire Door Mounted Sensor SuperScan displayed in this example harness labeled to the approach push side Door Mounted Sensor 3 Wire Door Mounted Sensor harness labeled to the safety swing side Door Mounted Sensor 4 Route wiring harness 20 5215 02 from the Door Mounted Sensor to DP Hub and plug into DP Hub at locati...

Page 5: ...ed or for more precise Home Switch installation please refer to Appendix C For a typical two door system 3 Snap the supplied magnet into the second Door Mounted Sensor extrusion end cap and install the end cap on the Door Mounted Sensor extrusion If you cannot use the typical installation there are several alternatives For more Home Switch information please refer to Appendix C 75 5652 01 20100830...

Page 6: ... of the device NOTE See Programming Parameter FA on page 10 section 6 1 Auxiliary Push Plate 10 Install Eagle s optional 1 For complete installation instructions refer to Eagle User s Guide 75 0058 2 Wire Eagle as displayed above 3 Mount Eagle Sensor to door header and route Eagle harness 20 5096 through door header and plug into DP Hub at location marked EG1 For two way traffic repeat the steps a...

Page 7: ...rness 20 5100 from the Receiver to DP Hub and plug into DP Hub at the other location marked BEAMS NOTE See Programming Parameter FB on page 10 section 6 1 NOTE If using beams the DP Hub will automatically be set to Advanced BodyGuard Safety 13 Install Power Harness 1 Install transformer in an easily accessible location to the DP Hub 2 Route wiring harness 20 5095 from the Transformer to DP Hub and...

Page 8: ... door system 1 Set FUNCT Fd to INCR 01 by first pressing the FUNCT button until DP Hub display shows Fd then press INCR button until display shows 01 Two door system 1 Set FUNCT Fd to INCR 02 default by first pressing the FUNCT button until DP Hub display shows Fd then press INCR button until display shows 02 NOTE The above step for showing how to check and or change a function is the same procedu...

Page 9: ...r Position System Learn After all of the programming has been performed to the DP Hub make sure that there is NO pedestrian traffic for approximately two minutes and 1 Make sure orange Home LED is on Make sure the ON OFF HOLD Switch is set to ON Then set the DP Hub into Learn Mode by first pressing the FUNCT and INCR buttons simultaneously until the blue LED comes on and then release both buttons ...

Page 10: ...ms This setting enables use of SBK 30 photoelectric beams Fn 00 to 30 Time in seconds 10 seconds Function Not Closed Timer This setting provides the amount of time that will be required to switch to the NOT CLOSED state This time is the amount that the door s has been allotted by the DP Hub for it to reach the CLOSED state from OPENED or MANUAL states FN is unused when FS 01 See FS below for furth...

Page 11: ...oor s learn For further explanation of the error codes and corrective actions please refer to Section 8 Troubleshooting E1 EDPS 1 baseline too low E2 EDPS 1 baseline too high E3 EDPS 2 baseline too low E4 EDPS 2 baseline too high E5 Door 1 door opened degrees too low 80 minimum E6 Door 1 door opened degrees too high 110 maximum E7 Door 2 door opened degrees too low 80 minimum E8 Door 2 door opened...

Page 12: ...yGuard if needed Check and change FL at DP Hub if needed Check wiring of BodyGuard Section 5 4 Error codes E1 E3 EDPS is not connected to DP Hub Check wiring of EDPS Section 5 7 EDPS is configured for 2 doors but is installed on a 1 door system Check function Fd at the hub If it only a 1 door system value should be set to 01 Faulty EDPS Replace EDPS Faulty DP Hub Replace DP Hub Error codes E2 E4 E...

Page 13: ...acrifice the safe operation of the automatic door or gate for an incomplete solution The following numbers can be called 24 hours a day 7 days a week For more information visit www beasensors com During normal business hours please contact us at Pittsburgh PA 800 523 2462 8 am 5 pm EST San Dimas CA 877 232 9378 8 am 5 pm PST After normal business hours please contact us at West Coast Mexico 888 41...

Page 14: ... 2 EMPTY 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 EMPTY 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 RED BLACK WHITE GREEN RED BLACK WHITE GREEN DOOR MTD SENSOR APPROACH SIDE DOOR MTD SENSOR SAFETY SIDE EMPTY 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 EMPTY 1 INHIBIT GND 2 INHIBIT 3 N C 4 N O 5 COM 6 POWER 7 POWER 8 RED BLACK WHITE GREEN RED BLACK...

Page 15: ...u can use the Home Switch LED orange on the DP Hub To use the Home Switch LED the DP Hub must be powered the magnetic reed switch must be wired into the EDPS and the EDPS must be plugged into the DP Hub Alternatively if you have a multimeter with continuity all you will need to do is remove the magnetic reed switch wires from the EDPS and connect them to your meter with it set to continuity 1 Loos...

Page 16: ...trusion and frame and route the wires into the extrusion then into the EDPS Another example would be to use the mechanical limit switch es on an equipped operator You could install separate wires and route them through the door to the EDPS or you could simply splice into the 8 pin connector on one of the EDPS harnesses at the DP Hub at the orange pin 3 and orange black pin 4 wires Note that if usi...

Reviews: