background image

 

14 

CIT 400 

pressure and level 

Menu level SinP - parameter of signal input (analogue input) 

The subordinate menu items are used to define the measurement span of the analogue input 
for 4 mA and 20 mA. 

Signal input - starting point of measuring range 

ZPIn 

The measurement value for the analogue input at 4 mA must be entered 

here. Normally this value is 0, which means 0 m at 4 mA in case of a 
pressure probe with a measurement range of 0 to 6 m water column 
height. Use the arrow keys to enter the numeric value and confirm with 
Enter. 

Signal input - end point of measuring range 

EPIn 

The measurement value for the analogue input at 20 mA must be en-

tered here. Normally this is the maximum measurement span, resulting 
from the example above, i. e. a value of 6. Use the arrow keys to enter 
the numeric value and confirm with Enter. 

Signal input - decimal point position 

dP 

Here you can define the decimal point position. Use the arrow keys to 

move the decimal point and confirm with Enter. 

Menu level Lin - parameter of the linearization 

Via this menu level, you can linearize the input signal (sensor) by a supporting point. This func-
tion is essential when the sensor signal is not linear to the output signal of the process transmit-
ter. By this function, it is possible to get an output signal nearly linear to the filling volume in ir-
regular shaped tanks. 

Linearization - activation / deactivation 

Lion/Liof 

With this menu, the linearization can be switched on or off. In the switch-

off mode, the supporting points are not taken into account. 

Linearization - number of supporting points 

In this menu, the number of supporting points has to be set. The permis-

sible range is set from 2 to 32 supporting points. 

Linearization - input signal of supporting points 

in n 

In this menu, the first part of the supporting points has to be defined, 

whereas "n" in the menu designation is replaced by the number of the 
supporting point (in 1, in 2, ... in32). The sensor signal of the respective 
supporting point which lies on the input must be entered. In the following 
menu, the corresponding output signal must be set. The input value is 
based on the scaling limits defined in the menu level 

SinP

Linearization - output signal of the supporting points 

ou n 

In this menu, the second part of the supporting points has to be defined, 

whereas "n" in the menu designation is replaced by the value of the re-
spective supporting point (ou 1, ou 2, ... ou32). The value has to be en-
tered corresponding to the value for reaching a supporting point. Be-
tween two supporting points, the course is linear. Please note that the 
supporting points must be entered in ascending sequence, i. e. the value 
for n+1 has to be higher than the value for n. The output signal on the 
analogue output is developed by the indicated value, whereas the pa-
rameters from the menu level 

Aout

 are used. 

Summary of Contents for CIT 400

Page 1: ...RS GmbH BD Sensors Straße 1 Telefon 49 0 92 35 98 11 0 www bdsensors de D 95199 Thierstein Telefax 49 0 92 35 98 11 11 info bdsensors de Operating manual CIT 400 Process Display ID BA_CIT400_E Version 10 2019 1 ...

Page 2: ... 3 Front panel mounting 6 3 4 Electrical installation 6 3 5 Installation example 8 4 Overvoltage protection 9 5 Operation 10 5 1 Operating and display elements 10 5 2 Menu operation 10 5 3 Description of the menu levels 11 5 4 Structure of the menu system 11 5 5 Menu list 13 6 Troubleshooting 18 7 Programming examples 19 7 1 Level measurement 19 7 2 Interface level measurement 20 7 3 In bounds out...

Page 3: ...le danger Non compliance may result in death or serious injury CAUTION Hazardous situation Non compliance may result in minor or moderate injury NOTE draws attention to a possibly hazardous situation that may result in property damage in case of non compliance Precondition of an action 1 2 Staff qualification Qualified persons are persons that are familiar with the mounting installation putting in...

Page 4: ...liability for any wrong selection and the consequences thereof The technical data listed in the current data sheet are engaging and must absolutely be com plied with If the data sheet is not available please order or download it from our homepage http www bdsensors de WARNING Danger through incorrect use In order to avoid accidents use the device only in accordance with its intended use 1 4 Limita...

Page 5: ...tely qualified persons who have read and understood the user manual NOTE For operation and maintenance work the operator is obligated to observe the infor mation on the warning signs possibly affixed to the device The transmitter mounting place has to be selected according to certain criteria Please avoid strictly direct sunlight use weatherproof cover if necessary heat emitting objects max ambien...

Page 6: ...d checked All outer circuits wires and lines connected to the device must have a minimum isolation re sistance of 250 V If the voltage exceeds 42 VDC a minimum isolation resistance of 500 kΩ is necessary The section dimension of the power supply wires must be 0 75 mm in accordance to IEC 227 or IEC 245 To observe the degree of ingress protection please refer to the technical data in the appendix T...

Page 7: ...7 www bdsensors de CIT 400 Standard top hat rail housing front panel housing Optionally top hat rail housing front panel housing Fig 2 Terminal clamps ...

Page 8: ... with alarm relay Fig 3 CIT 400 with 2 wire sensor Example 2 CIT 400 with analogue output supplied by a 3 wire sensor with alarm relay Fig 4 CIT 400 with 3 wire ultrasonic sensor Example 3 CIT 400 as transmitter when supplied with voltage signals from a pickup or to simulate an external sensor with voltage output at the CIT 400 Fig 5 CIT 400 with pickup feeding a mA signal Limit value message Rel ...

Page 9: ...the process transmitter Ener Pro 220 Tr for 230 V power supply of the process transmitter Leakage current 20 000 A and high capacity up to 16 A for safe and durable protection of several devices simultane ously Fig 6 Overvoltage protection of analogue inputs Fig 7 Overvoltage protection of analogue outputs Fig 8 Overvoltage protection of power supply Please pay attention to the non reversed connec...

Page 10: ...g item To leave a menu item push the Enter button To leave the menu system completely the last menu item has to be scrolled over or you will have to wait until the device changes automatically to display mode about 1 minute after pushing a button All settings are permanently stored in an EEPROM and there fore available again even after disconnecting the device from the supply voltage button with t...

Page 11: ...em The menu system and the menu items have been designed as simply as possible Each indi vidual menu item is described below in detail allowing a straightforward and quick configuration of your device The grey marked menus are not available in the standard version Please follow the manual meticulously and remember that changes of the adjustable pa rameters become only effective after pushing the O...

Page 12: ...nt relay 2 Menu S2on Reset point relay 2 Menu S2of Contact inverting relay 2 Menu In2 Switch on delay relay 2 Menu D2on Switch off delay relay 2 Menu D2of min measured value Menu ZPou Status relay 2 Menu R2Si Password setting Menu PAnr Adjusting signal input of span Menu SiSP max measured value Menu EPou Status alarm relay Menu ALSi Default setting Menu LoAD Status analogue output Menu AnSi On OFF...

Page 13: ...ue rang es between 0 and 100 and has a direct relation to the analogue out put of the transmitter which varies within a range of 4 to 20 mA depend ing on the value selected in menu outY Confirm with Enter after se lecting dlS4 in order to activate this display mode Display scaled measurement value with offset and display offset dIS5 Indicates the scaled measurement value with the added offset on t...

Page 14: ...ing volume in ir regular shaped tanks Linearization activation deactivation Lion Liof With this menu the linearization can be switched on or off In the switch off mode the supporting points are not taken into account Linearization number of supporting points n In this menu the number of supporting points has to be set The permis sible range is set from 2 to 32 supporting points Linearization input...

Page 15: ...level this value determines e g the turn on point In window mode in bounds out of bounds this value determines e g the in bounds upper switching point The value can be set using the arrow keys Confirm with Enter Contacts reset point S1of S2of S3of S4of This menu defines the lower switching point of the respective relay The programming example shows the function of this menu In hysteresis mode limi...

Page 16: ... 0 up to 6 meters the menu EPou can be set on 5 meters If the sensor reaches this value the output will be e g 20 mA if the signal range in menu outY was set to 4 20 mA Menu level tESt simulation testing mode In this menu level all test and simulation menus are located The simulation options cover a manual relay control as well as an analogue output signal simulation Simulation status of the relay...

Page 17: ... you should know the password PIN If this function is selected the unit will wait for PIN entry The function will not be executed until a correct entry of the password The default set ting for the password is 5 Please note that also the password is reset to default Menu level CAL calibration This level is for self calibration of the analogue input to the lower and upper sensor signal 4 20 mA You c...

Page 18: ...nsor damage and there fore interruption sensor damage current on analogue input below 3 3 mA check cable for damage exchange cable or sensor if necessary Err sensor electronics damaged supplying too high current cable short circuit or connection box causes current higher than 22 mA on analogue input due to humidity or damaged terminal clamps current on analogue input higher than 22 mA check cable ...

Page 19: ... 4 20 mA final peak of pen recorder 20 mA at 7 m The process transmitter has to indicate the max filling level of the tank 7 m Programming Select the menu dlS1 in the menu level dlSP Set the following values in the menu level SInP ZPIn 0 starting point of measuring range EPIn 10 end point of pressure range dP 2 decimal point position Set the following values in the menu level Aout outY 4 20 output...

Page 20: ...the menu contact invert ing In 1 and In 2 switch on point switch off point switch on point switch off point Programming Select the menu dlS1 in the menu level dlSP Set the following values in the menu level SinP ZPIn 0 starting point of measuring range EPIn 10 end point of pressure range dP 2 decimal point position Select the menu 1 in the menu level rELn and set the following values HY 1 CP 1 HYo...

Page 21: ...nu contact inverting In 1 and In 2 in bounds function out of bounds function Programming Select the menu dlS1 in the menu level dlSP Set the following values in the menu level SinP ZPIn 0 starting point of measuring range EPIn 10 end point of pressure range dP 2 decimal point position Select the menu 1 in the menu level rELn and set the following values HY 1 CP 1 CPon window mode S1on 4 switching ...

Page 22: ...mal point position Select the menu 1 in the menu level rELn and set the following values HY 1 CP 1 HYon hysteresis mode S1on 6 upper switching point 1 S1of 5 lower switching point 1 In1 In inverting of relay 1 d1on 10 switch on delay in seconds Select the menu 2 in the menu level rELn and set the following values HY 2 CP 2 HYon hysteresis mode S2on 6 upper switching point 2 S2of 4 5 lower switchin...

Page 23: ...on decalcification modifications or repair it has to be cleaned carefully and packed shatter proofed You have to enclose a notice of return with detailed defect description when sending the device If your device came in contact with harmful substances a declaration of decontamination is additionally required Appropriate forms can be downloaded from our homepage Download these by accessing www bdse...

Page 24: ... ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ______________...

Reviews: