Page
10
If you get the following response, type “n” and press Enter, if you want the unit to automatically switch-back to
the primary source. It will tell you the current delay time and you can change the delay time.
If you type ‘Y’ to DISABLE the switch-back, you will have to manually switch the input source by typing
‘source 1’ at the MMP100 prompt.
If you get the following response, type “y” and press Enter. Change the delay time if needed.
After pressing Enter you get to the configure menu.
Type ‘9’ at the prompt and press Enter to see the Brownout setting for Primary to Secondary. Then you will be
asked to set the Secondary to primary value..
Disable switch back to primary (Y/N)? N
Current delay switch back to primary source time is(0= minimum): 0 Seconds
Change delay switch back time (Y/N)?y
Enter seconds (0-6500):
Enable switch back to primary (Y/N)? y
Current delay switch back to primary source time is(0= minimum): 0 Seconds
Change delay switch back time (Y/N)?y
Enter seconds (0-6500):
1)...Manage Users
2)...Change Outlet Name
3)...Enable/Disable Confirmation
4)...Enable/Disable Status Menu
5)...Change Unit ID
6)...Change Alarm Threshold
7)...Change Display Orientation
8)...Change Redundant Power Switch Back mode/time
9)...Change Redundant Power Switching Brownout Voltage Levels
X)...Exit
Enter Request:
9
Primary to Secondary trip voltage value : 100.0 Volts
Modify (Y/N)?
Secondary to Primary return voltage value : 100.0 Volts
Modify (Y/N)?