6.1.
POWER AND CONNECTION WIRING
The connection cables must comply with the specifications listed in the table below.
WIRING SIZE
50
70
100
120
140
160
Indoor power supply wires
(mm
2
)
2x1,0+E
2x1,0+E
2x1,0+E
2x1,0+E
4x1,0+E
4x1,0+E
Outdoor power supply wires
(mm
2
)
2x2,5+E
2x4,0+E
2x6,0+E
2x6,0+E
4x1,5+E
4x1,5+E
Connection wires (mm
2
)
2x0,2+E
2x0,2+E
2x0,2+E
2x0,2+E
2x0,2+E
2x0,2+E
Connect the power supply to the outdoor unit and conduct the wring connection as shown
on the below diagram:
Model 50/70/100/120 (single-phase)
Model 140/160 (three-phase)
N.B.
-
The connection wire of indoor units should be connected to the corresponding
terminal board; otherwise it will cause the unit failure or even damage the units.
-
Connect the grounded wire correctly, otherwise will cause the malfunction of some
electrical component and shock or fire indeed.
-
Don't reverse the power polarity.
-
Must fix the screw nail of the firmly wire, then drag the wire lightly, confirmation
whether it's firmly.
6. WIRING