INSTRUCTIONS FOR FITTERS
71.05086.02 - EN
MAX. LENGTH
L1+L2 (
m)
POSITION OF
AIR
REGULATOR
CO
2
%
AFR
G20
G30
G31
NUVOLA3 COMFORT 280 Fi
0 ÷ 20
1
7,1
8,0
8,0
20 ÷ 30
2
16.4 HORIZONTAL SEPARATE FLUE INSTALLATION EXAMPLES
IMPORTANT
-
Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.
If the condensate collection kit is installed, the discharge duct must slope down towards the boiler.
(L1 + L2) max = 30 m
911231_4805
L max = 10 m
911231_4806
N.B.:
For the
C52
type, do not fit the flue and air duct terminals on opposite walls of the building. The air duct (for hori-
zontal flues) must have a maximum length of 10 metres (6 m for model 140 Fi).
If the discharge duct is longer than 6 metres, install the condensate collection kit, supplied as an accessory, near the boiler.
IMPORTANT:
if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct
passes through building walls.
For detailed installation instructions, consult the technical data provided with the accessories.
16.5 SEPARATE VERTICAL FLUE INSTALLATION OPTIONS