background image

16

© Baxi Heating UK Ltd 2006

Purge Pumps

It is possible that difficulty may be experienced removing air out

of the ground arrays, especially out of the top of each of the

“Slinky®” loops which consist of a large number of 1 metre

diameter loops of 1” bore pipe. This can also occur with vertical

(ie. drilled) arrays. All procedures for removing air from

slinkies® applies equally to removing air from underfloor

heating systems. Most underfloor heating manifolds have

fill/purge connections, and the same pump and procedure can

be used for underfloor as for slinkies®.

Why not just use mains water ?

A normal rising cold water main in a building has insufficient

flow to force out this air - typical flow rates from a cold tap are

around 10 to 30 litres per minute, which is less than half that

required. Also mains water is “aerated”. 

Why can’t I use an existing pump that I have ?

To remove the air from Slinky® ground arrays, a suitable pump

will be required. The longest slinky® trench is 50 metres, which

will contain a total of about 300 metres of pipe. To achieve the

minimum velocity through the slinky® pipes to remove the air,

a minimum pump power in excess of 1 kW is required. If you

are considering using an existing pump and it does not absorb

at least 1 kW then it will not be suitable. In addition, the pump

needs to have high-flow (at least 60 litres per minute) against a

pressure of at least 1 bar. To achieve this, a “multi-stage” type

of pump is needed, which is different to “normal” types of

water pump.

Where can I get hold of a suitable purge pump ?

We recommend the Clarke CPE130SS, part no. 051010379

from www.machinemart.co.uk or telephone 0845 450 2855.

The pump comes ready to take a 1” BSP fitting. A plumbers

merchant can supply a 2 x 1” BSP male iron to 28 mm

compression. This will enable the pump to be connected to the

slinky® manifold using 28 mm “Speedfit” or similar pipe and

elbows.

Any other tips ?

Before it will work, the pump itself needs to be purged of air by

removing the fill plug, and filling with water, along with both

connecting pipes. Fill the ground arrays with water as far as

possible, and pressurise them with mains water using the cold-

feed on the heat pump. Opening the valve between the slinky®

manifold and the water pump will force water through the

pump, into the dustbin, purging air out of the pump on the way.

It usually takes around 2 to 3 minutes of pumping for water to

go all the way through one slinky® and back to the dustbin. As

the Clarke CPE130SS will achieve up to 5 bar pressure against a

closed valve it is essential that the connections to the pump and

manifold are robust.

Clarke CPE130SS

Purge Pump

Summary of Contents for Geoflo

Page 1: ...UK Ltd 2006 Baxi Geoflo Single Compressor Compact Heat Pump Please keep these instructions in a safe place If you move house please hand them over to the next occupier Operation Installation Maintenance Instructions ...

Page 2: ... reserved No part of this publication may be reproduced or transmitted in any form or by any means or stored in any retrieval system of any nature including in any database in each case whether electronic mechanical recording or otherwise without the prior written permission of the copyright owner except for permitted fair dealing under Copyrights Designs and Patents Act 1988 Applications for the ...

Page 3: ...uld be taken when moving it Check the appliance for transport damage Under no circumstances should a damaged appliance be operated or installed It is dangerous to modify this appliance in any way Ensure that the appliance does not stand on the electrical supply cable If the supply cable is damaged it must be replaced Ensure that the appliance and any metal pipes are properly earthed A water treatm...

Page 4: ...g Heateam please have the following information to hand Geoflo system serial number Geoflo system model number Your installer name address details and contact details Proof of purchase if you do not have the Geoflo serial number What this warranty covers Free of charge repair or replacement of components found to be faulty from manufacture Free of charge replacement of the complete assemblies excl...

Page 5: ...5 Baxi Heating UK Ltd 2006 Technical Data ...

Page 6: ...erfloor pressure gauge reads at least 0 3 bar If the pressure is lower than this find the mains cold water supply valve which is probably near your underfloor heating manifold fully until the gauge reads at least 1 8 bar at which point a click will be heard Close the mains cold water supply valve fully If you can t find this valve or when you open it the gauge reading does not increase call your i...

Page 7: ...7 Baxi Heating UK Ltd 2006 Operating Instructions Trouble shooting P Pr rg g S Se el l ...

Page 8: ...8 Baxi Heating UK Ltd 2006 Elevation of typical installation ...

Page 9: ...9 Baxi Heating UK Ltd 2006 Recommended Installation Clearances All dimensions in millimetrs ...

Page 10: ...10 Baxi Heating UK Ltd 2006 Hood Removal Clearances All dimensions in millimetrs ...

Page 11: ...11 Baxi Heating UK Ltd 2006 ...

Page 12: ...12 Baxi Heating UK Ltd 2006 ...

Page 13: ...13 Baxi Heating UK Ltd 2006 Slinky Manifold Connections ...

Page 14: ...14 Baxi Heating UK Ltd 2006 Pumbing Connections ...

Page 15: ...15 Baxi Heating UK Ltd 2006 Output Pump Bleed Port ...

Page 16: ...nd it does not absorb at least 1 kW then it will not be suitable In addition the pump needs to have high flow at least 60 litres per minute against a pressure of at least 1 bar To achieve this a multi stage type of pump is needed which is different to normal types of water pump Where can I get hold of a suitable purge pump We recommend the Clarke CPE130SS part no 051010379 from www machinemart co ...

Page 17: ...17 Baxi Heating UK Ltd 2006 Purging the Ground Arrays ...

Page 18: ...18 Baxi Heating UK Ltd 2006 Underfloor Heating Wiring Connections Single Manifold smaller building Multiple Manifold larger building ...

Page 19: ...19 Baxi Heating UK Ltd 2006 Control Box Layout ...

Page 20: ...20 Baxi Heating UK Ltd 2006 Wiring Connections ...

Page 21: ...ion The wires can be connected either way round Avoid routing this cable with any other cables to prevent interference 10 Check and rectify any leaks that may be in the plumbing system 11 Remove the plastic blanking plugs and connect the purge pump to the fill and purge ports on the Slinky Manifold see Purging the ground arrays Keep the isolating valve to the heat pump closed The purge ports can b...

Page 22: ...re so that any leaks will immediately become apparent 21 In order to activate the software controller both the ground and underfloor circuits must be taken above 1 8 bar water pressure 22 Remove the purging equipment and the handles from the valves on the manifold to ensure they cannot be inadvertently operated and place the plastic blanking plugs back in the slinky manifold 23 Find the cold fill ...

Page 23: ...Notes 23 Baxi Heating UK Ltd 2006 Notes ...

Page 24: ... 261 Website www baxi co uk e oe company All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our standard Conditions of Sale which are available on request ...

Reviews: