18
© Baxi Heating UK Limited 2005
7.0 Site Requirements
7.11
Flue Options
1. The Baxi Combi 105 HE can be fitted with flue
systems as illustrated.
2. The standard flue is suitable only for horizontal
applications.
3. Maximum permissible equivalent flue lengths are:-
Horizontal Concentric
3m
Vertical Concentric
3m
Vertical Twin Pipe
12m
4. Any additional “in line” bends in the flue system must
be taken into consideration. Their equivalent lengths
are:-
Concentric Pipes:
45° bend
0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
45° bend
0.25 metres
91.5° bend
0.50 metres
The elbow supplied with the standard horizontal flue is
not included in any equivalent length calculations
6. The illustrations opposite show examples of
maximum equivalent lengths.
7. Full details of part numbers and descriptions of all
optional flue components and kits can be found in the
Baxi Flue Guide.
8. Instructions for guidance and fitting are included in
each kit where appropriate.
NOTE: Flue length is measured from point A to B
as shown.
Horizontal
Flues
Vertical
Flues
Vertical
Flues
(Twin Pipe)
B
A
B
A
B
A