background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

Installation Instructions – Page 4

GAS SUPPLY

1. The gas supply is provided from the service tap on the boiler
unit. A supply pipe is provided with the fire. This pipe has one
flared end for connection to the fire and a plain end which is
connected to the service tap by a nut and olive.
2. Dependent upon the position of the boiler relevant to the
surround or wall finish face, it may be necessary to shorten the
supply pipe. IF THE PIPE HAS TO BE SHORTENED CARE
MUST BE TAKEN. The length of the supply pipe is determined
as follows:

(a)

Measure the distance ‘D’ from the centre of the front
positioning ‘V mark on the boiler tray, back to the
surround face or finished wall face (Fig.3).

(b)

FROM THE PLAIN END of the supply pipe cut off a
length of pipe equal to the distance ‘D’ measured
above. Take care to ensure that the cut is square
and the pipe is free from burrs and swarf.

ALTERNATIVELY

(c)

The amount of pipe required to be cut off can be
determined by holding the PLAIN END of the pipe
against the surround or finished wall face, marking
the pipe at the position of the centre of the front
positioning ‘V mark on the boiler tray.

3. After threading the steel flare nut on the above pipe, connect
the plain end to the service tap with the remaining nut and olive.
It is important to ensure that the flared end of the pipe:

(a)

Faces to the right.

(b)

Is parallel with the hearth or floor.

4. It is necessary to unscrew and remove the extension plate
from the boiler controls heat shield. Once removed this item can
be discarded (Fig.4).

Fitting the Fire

HEARTH FIXING

1. Fit the fire backing plate to the fire using the M5 x 8mm
thread forming screws provided (Fig.5).

2. Locate the fire spigot into the draught diverter on the boiler.
Push the fire backwards until the backing plate touches the
surround or finished wall face. Adjust the feet to level the fire
(Fig.6).

3. Mark the position of the most suitable pair of securing holes
in the fire backing plate (Fig.5) and remove the fire. Drill and
plug the wall with suitable plugs. Replace the fire and secure to
the wall with suitable fixing screws.

4. Connect the supply pipe to the fire inlet connection.

WALL FIXING

1. Slide the fire support plate over the overhanging boiler base
(Fig.4). Using the screws provided, loosely attach the plate
using the slots at each side.

2. On electronic control boilers it will be necessary to remove
the input plug from the controls. Push the support plate
backwards until it touches the wall surface and tighten the
screws to lock the frame in position. Locate the fire spigot into
the draught diverter on the boiler. Push the fire backwards until
the backing plate touches the finished wall face. Adjust the feet
to level the fire (Fig.6).

3. Mark the position of the most suitable pair of securing holes
in the fire backing plate (Fig.5) and remove the fire. Drill and
plug the wall. Replace the fire and secure to the wall with the
two fixing screws provided.

4.Connect the gas supply pipe to the fire inlet connection.

Summary of Contents for Bermuda SL3

Page 1: ...Supplied By www heating spares co Tel 0161 620 6677 Baxi Bermuda SL3 Fireside Gas Central Heating Unit Comp No 237883 Issue 4 1 00 Installation and Servicing Instructions ...

Page 2: ...e G C No 37 075 02A fire is controlled by a knob positioned on the right hand side For use with the following boilers of the case Ignition is by piezo spark to the pilot Fig 13 Bermuda 401 Bermuda 45 4 M For details of Propane appliances see back page G C No 44 077 49 G C No 44 077 71 Bermuda 552 Bermuda 45 4 E The control knob has six positions giving a choice of four G C No 44 077 50 G C No 44 0...

Page 3: ...e opening and at the same level as the base of the builders opening The top surface of the hearth should be a minimum of 50mm 2 in above floor level and must be level with the base of the opening On no account should the fire unit be fitted directly onto a combustible floor or carpet Surround or Wall Finish Figs 1 and 2 The wall behind the fire must be non combustible The surround or wall finish m...

Page 4: ...earth or floor 4 It is necessary to unscrew and remove the extension plate from the boiler controls heat shield Once removed this item can be discarded Fig 4 Fitting the Fire HEARTH FIXING 1 Fit the fire backing plate to the fire using the M5 x 8mm thread forming screws provided Fig 5 2 Locate the fire spigot into the draught diverter on the boiler Push the fire backwards until the backing plate t...

Page 5: ...position 3 fully anti clockwise The pressure should be 14 5mbar 0 5mbar 5 8 in wg 0 2 in wg 8 Turn the control knob clockwise to the OFF position Remove the pressure gauge and refit the pressure test point sealing screw ensuring a gas tight seal 9 Test for clearance of flue products as follows a Ensure that all doors and windows are closed IMPORTANT NOTE If there is an extractor or ceiling fan in ...

Page 6: ...Supplied By www heating spares co Tel 0161 620 6677 Commissioning the Fire Page 6 ...

Page 7: ...ner as follows Figs 10 and 11 i Disconnect the compression nuts from the injectors ii Remove the 2 screws securing the burner and remove the burner out over the support bar iii Using a soft brush remove all deposits from the top of the burner and the burner ports 9 Remove and clean or replace the injectors as necessary Do not use a pin or wire for cleaning purposes 10 Clean any lint or debris from...

Page 8: ...rbs 4 COAL BED Fig 11 Remove the glass front panel as described above Remove the coal bed by carefully lifting it away from the locating pins On re assembly ensure that the coal bed is correctly located over the locating pins CAUTION The coal bed is extremely fragile and must be handled accordingly Gloves should be worn and any inhalation of the dust should be avoided Keep the coals away from chil...

Page 9: ... Height 706mm to hearth see page 6 Fig 9 Width 696mm for clearances Depth 317mm Weight 34kg unpacked HEAT INPUT 5 70kW 19 450 Btu h HEAT OUTPUT 3 6gkW 12 590 Btu h GAS GROUP G20 Natural Gas INJECTOR SIZE 230 F11 SETTING PRESSURE Cold 14 5 0 5mbar 5 8 0 2in wg THERMOCOUPLE OUTPUT 9 4 1 3mV ...

Page 10: ...Supplied By www heating spares co Tel 0161 620 6677 Bermuda SL3 Baxi Heating Ltd page 10 Fault Finding Chart Page 10 11 BAXI BERMUDA SL3 Gas Type G20 Natural Gas ...

Page 11: ... 155 758 040955 20 Knob Gas Tap Control 156 430 234544 75 Flame Failure Device Gas Tap Concentric TE SA 809 378 916 238966 76 Piezo Unit 393 734 042941 80 Encapsulated Unit Concentric TE 41 8 384 248 082462 87 230 F11 Injector 381 879 092133 88 Burner Aeromatic Baxi Special 155 949 043210 90 Lead Electrode 378 911 236209 94 Coal Bed 156 429 235149 77 Pilot Filter 205 723 082412 84 Pilot A S D Asse...

Page 12: ...t shield provided with Bermuda 57 3 M G C No 44 077 63 the boiler and fit the new controls heat shield using the Bermuda 57 3 E G C No 44 077 62 screws previously removed Bermuda 45 4 M G C No 44 077 71 Bermuda 45 4 E G C No 44 077 73 Check the data badge on the back boiler If the boiler Bermuda 57 4 M G C No 44 077 72 internal wiring is not depicted take the foil label from the kit Bermuda 57 4 E...

Page 13: ...fire is being used with a Bermuda 401 boiler unit the support brackets from the previous plate must be fitted before the fire support plate can be fixed in place Push the support plate backwards until it touches the surround or wall face and tighten the screws to lock it in position BERMUDA 45 3 57 3 45 4 57 4 Take the fire support plate from the fire unit packaging and loosely attach it above the...

Page 14: ...e for use with Bermuda 553 Propane Back Boiler appliances The instructions supplied with the back boiler contain details of gas supply requirements and electrical connections All site requirements and installation details can be found earlier in this booklet NOTE When removing the burner it is necessary to remove the right hand retaining screw and the left hand coal bed retaining pin which also re...

Reviews: