8.0
Installation - Page 19
8.4 Fitting The Boiler
(Fig. 24)
1. Remove the tape from the tap rail on the support bracket
and fit the central heating return filter (Fig. 25).
2. Lift the boiler using the lower edges of the combustion
box.
3. Lift the boiler over the support bracket and engage onto
the top hooks.
4. To gain access to the connections between boiler and
valves, release the facia securing screws (¼ turn) and hinge
down the facia box.
5. Make the gas connection first. This will centralise the
boiler. The gas sealing washer is an integral part of the gas
tap.
6. Insert the fibre sealing washers between the valve outlet
face and the flange on the copper bends of the water circuit
connections.
7. Tighten the connections.
8.5 Making the Condensate Drain Connection
1. Connect the condensate drain using the 1” BSP nut and
seal supplied. (see section 7.8.)
2. For better access, loosen the left hand electrical
box/transformer mounting plate securing screws and remove
the right hand securing screw. Slide the electrical box to the
right (Fig. 25b).
NOTE: To ensure the correct operation and integrity of
the condensate drainage system
- Carefully pour approximately 1 litre of water into the
flue products exhaust, at the top of the heat exchanger
(Fig. 25a).
Check the condensate drain for leaks, blockage and fall.
Summary of Contents for Barcelona System
Page 7: ...4 0 Technical Data Page 7 ...
Page 8: ...5 0 Dimensions and Fixings Page 8 ...
Page 23: ...9 0 Electrical Page 23 ...
Page 24: ...9 0 Electrical Page 24 9 2 Illustrated Wiring Diagram ...
Page 38: ...14 0 Fault Finding Page 38 ...
Page 39: ...14 0 Fault Finding Page 39 ...
Page 40: ...14 0 Fault Finding Page 40 ...
Page 41: ...14 0 Fault Finding Page 41 ...
Page 42: ...14 0 Fault Finding Page 42 ...
Page 43: ...14 0 Fault Finding Page 43 ...
Page 44: ...Barcelona System Baxi Heating Ltd 44 45 14 0 Fault Finding Page 44 45 ...
Page 45: ......