14.0
Commissioning of solar controller
32
© Baxi Heating UK Ltd 2011
14.5
Menu “Programming”
All adjustable parameters can be checked in this menu and, if
necessary, changed. The default factory setting will usually give
efficient and problem free operation. However Baxi recommend
the following parameters marked * must be left at the default
settings. Any change to the Baxi recommended settings will
invalidate the warranty.
For more information or guidance please contact the Technical
Enquiries.
Indication
Description
Value range
Defaults
max
Storage 1/2:
15..95ºC
65ºC *
65ºC
Maximum temperature
dT max
Storage 1/2: Hysteresis (dT on)
3..40 K
7 K
7 K
dT min
Storage 1/2: Hysteresis (dT off)
2..35 K
3 K
3 K
min
Setting the speed control of the pump
30%..100%
100%
100
100% = speed control off
min
Temperature start for the function
20..90ºC
40ºC
40ºC
heating
dT
Hysteresis heating
1..30K
10K
10K
min
Start time 1
0:00...
00:00
(1)
00:00
for the independent controller
23.59
max
Stop time 1
0:00...
23:59
(1)
23:59
for the independent controller
23:59
min
Start time 2
0:00...
00:00
(2)
00:00
for the independent controller
23.59
max
Stop time 2
0:00...
23:59
(2)
23:59
for the independent controller
23:59
min
Start time 3
0:00...
00:00
(3)
00:00
for the independent controller
23.59
max
Stop time 3
0:00...
23:59
(3)
23:59
for the independent controller
23:59
min
Start time 4
0:00...
00:00
(4)
00:00
for time controlled circulation
23.59
max
Stop time 4
0:00...
23:59
(4)
23:59
for time controlled circulation
23:59
13:21
Clock
0:00...23.59
12:00
2
Press or to scroll
up or down to the required sub function.
The icon will flash, press to
select the function. Reset by pressing
or for
increase/decrease values. Press
and appears,
press to confirm and
disappears.
ok?
ok?