![Baxi 45 HTE Installation, Operation And Maintenance Manual Download Page 136](http://html.mh-extra.com/html/baxi/45-hte/45-hte_installation-operation-and-maintenance-manual_2711664136.webp)
68
912.359.1 - IE
IstructIons pErtaInIng to thE InstallEr
Table 2.2
Gas consumption at 15 °C
HTE
HTE
HTE
HTE
1013 mbar
85
100
120
150
Gas G20 - 2H - 20 mbar
pCI
mJ/m
3
34.02
34.02
34.02
34.02
Consumption at max. heat output
m
3
/h
9.26
10.9
13.08
16.35
Consumption at min. heat output
m
3
/h
3.50
3.89
4.23
4.39
Gas nozzle
mm
11.5
12
11
11.5
Co
2
max. heat output
%
8.7
8.7
8.7
8.7
Co
2
min. heat output
%
8.6
8.6
8.4
8.4
pout pressure at minimum power
pa
-
-
-4
-5
parameters
h536-h613
(rpm) at maximum power
5100
5650
4650
6000
parameters
h541-h610
(pwm %) at maximum power
75
100
55
100
parameter
h612
(rpm) at minimum power
1900
2100
1600
1550
parameter
h609
(pwm) at minimum power
15
15
10
9.5
parameter
h611
(rpm) ignition load
3600
3600
2600
2900
length of exhaust flue : 0 ÷ 10 m
parameter
h608
(pwm) ignition load
30
30
15
15
length of exhaust flue : 10 ÷ 20 m
parameter
h608
(pwm) ignition load
40
40
20
20
table 2.1
Gas consumption at 15 °C
HTE
HTE
HTE
HTE
1013 mbar
85
100
120
150
gas g31 - 3p - 37 mbar
pCI
mJ/Kg
46.34
46.34
46.34
46.34
Consumption at max. heat output
Kg/h
6.77
7.97
9.56
11.95
Consumption at min. heat output
Kg/h
2.57
2.86
3.10
3.22
Gas nozzle
mm
7.8
7.8
7.8
7.8
Co
2
max. heat output
%
10.2
10.2
10.2
10.2
Co
2
min. heat output
%
9.3
9.8
10.2
10.2
pout pressure at minimum power
pa
-
-
-7
-8
parameters
h536-h613
(rpm) at maximum power
4600
5150
4300
5350
parameters
h541-h610
(pwm %) at maximum power
75
100
55
100
parameter
h612
(rpm) at minimum power
1900
1950
1450
1450
parameter
h609
(pwm) at minimum power
14.5
14.5
10
9.5
parameter
h611
(rpm) ignition load
4200
4200
2600
2900
length of exhaust flue : 0 ÷ 10 m
parameter
h608
(pwm) ignition load
40
40
15
15
length of exhaust flue : 10 ÷ 20 m
parameter
h608
(pwm) ignition load
50
50
20
20