63
912.359.1 - IE
IstructIons pErtaInIng to thE InstallEr
c) with AGU2.500 for control of a low temperature system:
Refer to the instructions provided with the AGU2.500 accessories for connection and control of a low tempe-
rature zone.
In this case some electronic parameters must be modified (see §14)
(H552-H553-H632)
.
The electrical connection and settings needed to control a system divided into zones vary depending on the
accessories connected to the boiler.
a) Without QAA73 room temperature control device:
The contact relating to the request for operation of the various zones must be parallel-connected and connected
to terminal 3-4 “TA” of terminal block M2 in figure 10. The jumper present must be removed.
The central heating temperature is selected directly on the boiler control panel in accordance with the instruc-
tions provided for the user in this manual.
b) with QAA73 room temperature control device:
The pump relating to the room controlled by the QAA73 temperature control device must be supplied with
electricity by means of terminals 11-12 of terminal block M3 in figure 10.
The contact relating to the request for operation of the other zones must be parallel-connected and connected
to terminal 3-4 “TA” of terminal block M2 in figure 10. The jumper present must be removed.
The central heating temperature of the zone controlled by the QAA73 is set automatically by the QAA73 it-
self.
The central heating temperature of the other zones must be selected directly on the boiler control panel.
In this case some electronic parameters must be modified
:
H552 = 50, H632 = 00001111 (see §14).
Figure 10
c) with AGU2.500 for control of a low temperature system:
Refer to the instructions provided with the AGU2.500 accessories for connection and control of a low tempe-
rature zone.
In this case some electronic parameters must be modified (see §14)
(H552-H553-H632)
.
12.6 connecting a zone system
0702_0501 / CT_0675
1 ZONE
(QAA73)
n ZONE
(ROOM THERMOSTAT)
3 ZONE
(ROOM THERMOSTAT)
2 ZONE
(ROOM THERMOSTAT)
1 ZONE PUMP
BOILER
CIRCULATING
PUMP
BoIler
pump
HeAtIng Cut-out
relAy
2 zone-
pump
3 zone-
pump
n zone-
pump