3. APPLIANCE DATA
Under no circumstances is this fire to be converted to LPG. An LPG conversion kit does
not
exist for this gas fire.
The appliance data label is located on a plate at the base of the fire. This can be seen by
lifting the bottom front cover of the fascia.
This product uses fuel effect pieces containing Refractory Ceramic Fibres (RCF),
which are man-made vitreous silicate fibres. Excessive exposure to these materials
may cause irritation to eyes, skin and respiratory tract. Consequently, it is
important to take care when handling these articles to ensure that the release of
dust is kept to a minimum. To ensure that the release of fibres from these RCF
articles is kept to a minimum, during installation and servicing we recommend that
you use a HEPA filtered vacuum to remove any dust and soot accumulated in and
around the fire before and after working on the fire. When replacing these articles
we recommend that the replaced items are not broken up, but are sealed within a
heavy duty polythene bag, clearly labelled as RCF waste. RCF waste is classed as a
stable, non-reactive hazardous waste and may be disposed at a landfill licensed to
accept such waste. Protective clothing is not required when handling these articles,
but we recommend you follow the normal hygiene rules of not smoking, eating or
drinking in the work area and always wash your hands before eating or drinking.
This appliance does not contain any component manufactured from asbestos or asbestos
related products.
Page 6
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Gas
Natural (G20)
Inlet Pressure
20mbar
Input Max. (Gross)
5.1kW (17,400 Btu/h)
Input Min. (Gross)
3.0kW (10,236 Btu/h)
Inlet Test Pressure (Cold)
20.0 ± 1.0mbar (8.0 ± 0.4in w.g.)
Gas Connection
8mm pipe
Burner Injector
Stereomatic Cat. 82 Size 065
Pilot & Atmosphere Sensing Device
Copreci Ref. O.D.S 21500/166
Ignition
Integral piezo (Mounted on gas valve)
Aeration
Non-adjustable