hotbox must be kept away from the area which will be taken by the hotbox when it is
installed. Note that the centre of the appliance inlet ‘T’ connector is 25mm above the
fireplace floor. The inlet ‘T’ connector should be fitted to the supply pipe at this stage.
9. PREPARING APPLIANCE FOR INSTALLATION
1.
Remove the two screws to the side of the burner unit.
2.
Detach the burner unit from the hotbox by lifting clear.
3.
It is important that the grommet supplied in the
loose parts pack is fitted to the hole in the rear of the
convection box.
4.
For concealed connection only: Pierce the grommet to
allow the pipe to pass through it. The grommet should
envelop the pipe. If the hole is larger than the pipe, seal it
with tape.
Do not pierce the grommet unless the supply
pipe is to pass through it
.
5.
The appliance is supplied with two fireback spacers.
Do
not fit the fireback spacers if the fire is to be installed
into a precast or clay flue block system as in section
4.2.4
. These should extend backwards to ensure sufficient
clearance from the back of the fireplace. Remove the label
and retaining screws from the rear sides of the hotbox.
Position the fireback spacer as shown in
figure 9. Secure the fireback spacers using
the screws removed previously and the two
supplied with the fire.
6.
This appliance is supplied with a flue
restrictor for use where the flue draught is
excessive. The restrictor must NOT be fitted
where a precast flue or a flue liner is used.
For all other installations the restrictor should
be fitted. There may however, be certain
exceptional circumstances where fitting the
restrictor causes the fire to fail the spillage
test. In such cases the restrictor will have to
be removed. After removal conduct the
spillage check again.
The restrictor is packed loose with the appliance and is fixed with two screws (See
figure 10).
7.
Supplied with the fire is a spacer frame. This is made up of three separate pieces, a
top and two sides. The three pieces are identified in figure 11.
Page 18
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 10. Flue restrictor
Figure 9. Fireback
spacers