Installation
Mono Power Unit BUM 62 T
27
Baumüller Nürnberg GmbH
5.99009.03
y
You achieve the smallest possible effective antenna height by laying the cable directly on the ground
of the metallic rack.
y
You should lay all cables as close as possible to the conductors of the ground system to reduce the
effective loop area for magnetic coupling.
y
When laying signal and control cables in parallel across power cables, maintain a minimum distance
of 20 cm between the conductors.
y
Cables of different EMC categories should only cross at an angle of 90°.
y
For symmetrical signal transmission (e.g. differential amplifier inputs for the speed setpoint), twist
the conductors of each pair together and twist the pairs of wires together.
y
The connection between converter and ground plate should be as short as possible (<50 cm). Use
large cross-sections (>10 mm
2
)
y
Sources of noise such as fuses, transformers, chokes and noise-sensitive modules such as
microprocessors, bus systems, etc. should be located at least 20 cm away from the converter and
its cabling.
y
Avoid reserve loops on long cables.
y
The grounding of reserve wires in cables is mandatory (additional screening, avoidance of
capacitively coupled, hazardous contact voltages).
Summary of Contents for BUM 62 T
Page 1: ...E 5 99009 03 Manual BUM 62 T Mono Power Unit ...
Page 6: ...6 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 10: ...Safety notes 10 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 18: ...Transportation Unpacking 18 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 22: ...Assembly 22 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 48: ...Installation 48 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 62: ...Commissioning 62 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 66: ...Maintenance 66 Mono Power Unit BUM 62 T 5 99009 03 Baumüller Nürnberg GmbH ...
Page 73: ......