Description of the Software Modules and Parameters
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
53
3
1.3
System Ticks RT2
Display of the value of a counter which is incremented in TASK_RT2 by the ratio
TASK_RT2/TASK_RT1, so that System Ticks RT2 and System Ticks RT1 have approx-
imately the same value.
1.8
RT0-Cycle Time
Axis units:
The parameter for the cycle time for the RT0 time slice (for position and speed control-
lers and motor control) can be set here.
The value must be between 62.5 µs and 1 ms; the standard value is 250 µs.
The RT0-Cycle time can be changed only when the drive is inhibited.
The RT0-Cycle time must not fall below the preset current controller cycle time
. This is monitored and as the case may be the error 501 will be triggered
which inhibits the enable of the drive.
1.10
Task fieldbus cycle time
The parameter displays the cycle time for the task fieldbus.
The task fieldbus cycle time must not fall below the RT0-Cycle time. In this case the task
fieldbus cycle time is limited to the RT0-Cycle time, the error 505 will be triggered and thus
the enable of the drive will be inhibited.
102.1
Firmware number
Internal Baumüller firmware number
102.2
Firmware version
Display of the firmware version with 2 digits for main version (incompatible version), sub-
version (compatible version) and bugfix version.