Display- and operating elements BM3200, BM3300
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
Baumüller Nürnberg GmbH
64
4.5
4.5.3
Function of the LEDs H31/H32 and H41/H42
Depending on the variant of the fieldbus connection
LEDs EtherCAT
®
Type code
BM3200, BM3300
with EtherCAT
®
CoE profile:
BM3XXX-XXXX-XXXXX[-X]-
1
XXXX[-S0X]-XX[-XX][-EXX][-#XX]
Type code
BM3200, BM3300
with EtherCAT
®
SoE profile:
BM3XXX-XXXX-XXXXX[-X]-
7
XXXX[-S0X]-XX[-XX][-EXX][-#XX]
LEDs VARAN
Type code
BM3200, BM3300
with VARAN:
BM3XXX-XXXX-XXXXX[-X]-
2
XXXX[-S0X]-XX[-XX][-EXX][-#XX]
Naming on the
front plate
H31 (green)
H41 (green)
LINK
On:
connection between 2 PHYs
(physical interfaces) is established
H32 (yellow)
H42 (yellow)
ACTIVE
On:
data is received or transmitted
Designation
front plate
Meaning
Blinking pattern
H31 (green)
X3 Link / Act
off:
no connection
on:
connection
blinking:
data transmission
H32 (orange)
ERROR
on:
ERROR
(recipient error Phy1/Phy2)
H41 (green)
X4 Link / Act
off:
no connection
on:
connection
blinking:
data transmission
H42 (orange)
RUN
off:
ERROR/INIT
500 ms on/
500 ms off: PREOPERATIONAL
200 ms on/
1 s off:
SAFEOPERATIONAL
on:
OPERATIONAL
Meaning
Blinking pattern
Summary of Contents for b maXX 3000