TA200
www.baumer.com
19
Terminal assignment
Terminal
Function
1
2
3
4
5
6
7
8
9
Not assigned
Voltage supply (-)
Voltage supply (+)
Sensor supply 0 V
Sensor 24 V
–
–
Signal f1
_
For protection against shock hazards as specified in EN 61010, stran-
ded conductors may only be connected using wire end ferrules with
insulating caps. Terminals which are not assigned in the factory must
not be otherwise assigned by the user. We recommend shielding all
sensor connecting leads and earthing the shield at one end. Earthing
at both ends is recommend to avoid RF interference or if equipo-
tential bonding conductors are installed over long distances. Sensor
connecting leads should not be laid in the same trunking as the
mains power supply cable and output contact leads.
3.1 Connecting voltage supply
For alternating current
It is possible to switch between two different alternating voltage
ratings as required using the voltage changeover switch accessible
from the side of the device. The higher of the two alternating voltage
ratings (48 V or 230 V) is set in the factory.
115 VAC
(24 VAC)
230 VAC
(48 VAC)
➜
Set the required alternating voltage at voltage selector switch.
➜
Connect alternating voltage to terminals 2 and 3 in accordance
with the terminal diagram.
Voltage supply AC
Recommended external fusing
24 VAC ±10 %, 50/60 Hz
T 400 mA
48 VAC ±10 %, 50/60 Hz
T 400 mA
115 VAC ±10 %, 50/60 Hz
T 100 mA
230 VAC ±10 %,
50/60 Hz
T 100 mA
For direct voltage
Connect an interference-free supply voltage, i.e. do not use the
supply voltage for the parallel connection of drive systems,
contactors, solenoid valves etc.
➜
Connect direct voltage in accordance with the terminal diagram.
Supply voltage DC
Recommended external fusing
24 VDC ±10 %, max. 5 % RW
T 500 mA
Summary of Contents for TA200
Page 14: ...TA200 14 www baumer com ...
Page 28: ...TA200 28 www baumer com ...