MNL-126509
April 4, 2013
Page 109
8.2.2
Installation of the Compressor Unit
8.2.2.1
General
The floor site must be capable of supporting the weight of the unit. Secure the compressor unit to the
floor using ½” lag bolts. Position the unit so that it is level. Permissible inclination of the compressor unit
is listed in Paragraph 1.4.
If equipped with machine leveling feet, ensure the unit is leveled to prevent movement when operating.
Raise the unit with a forklift or crane to raise the unit at the leveling foot. Loosen the locking nut and turn
the leveling bolt clockwise to desired height. Lock the leveling foot in place with the provided hex-nut
once the desired height is achieved. Set the unit back down on the floor and check adjusted height. If fur-
ther adjustment is needed repeat.
Ensure that the compressor air intake is supplied with fresh air. The intake air must not contain any
exhaust fumes or flammable vapors such as paint solvents, which may cause an internal fire. Make sure
that the intake air is unobstructed and moisture in the intake air is kept to a minimum. It is important that
units draw in clean air. The quality of the incoming air determines the quality of the compressed air. This
is important even for industrial air, as any incoming fumes will also be compressed and will increase the
toxicity to anyone working with the compressed air.
If a remote control is provided, the unit must be equipped with a clearly visible plate warning the possi-
bility of the unit starting. As an additional measure, anyone starting the unit by remote control must make
sure that no one is checking or operating the unit. For this purpose, a second warning plate should be pro-
vided at the remote control unit.
^
CAUTION
The inclination values listed in Paragraph 1.4 are valid only if the oil level of the compressor is level with
but does not exceed the upper mark of the oil dipstick or oil level sight glass.
Figure 8-2
Leveling Feet
Before Raising
Leveling
Bolt
Locking
Nut
Leveling
Foot
After Raising